EdilKamin 809540 Installation, Use And Maintenance Manual page 13

Pellet fireplace
Table of Contents

Advertisement

THE FLUE
THE FLUE:
Further to the general prescriptions for the fumes duct
and flue, the flue: :
must serve solely to exhaust fumes
must be correctly sized to satisfy the requirements
of fumes exhaust (EN 13384-1)
should preferably be insulated, in steel with a
circular internal section. If rectangular, the corners
must have a radius of not less than 20 mm, with a
ratio of the internal dimensions of <1.5
must normally be at least 1.5 metres in vertical
length
must have a constant cross section
must be waterproof and thermally insulated to
ensure a good draw
must preferable have a collection chamber for
If pre-existing, must be clean, to prevent the fire
hazard.
in general, we recommend fitting a tube inside the
existing masonry chimney if its diameter is greater
than 150 mm.
INTUBATED SYSTEM
INTUBATED SYSTEM:
Further to the general prescriptions for the fumes duct
and flue, the intubated system:
must operate in negative pressure;
must be open to inspection
must observe local regulations.
THE CHIMNEY POT
THE CHIMNEY POT
must be windproof
must have an internal cross section equivalent to
that of the flue and a fumes outlet at least double
that of the interior of the flue
for dual flues (which should be spaced at least 2
m apart) the chimney pot receiving the fumes from
the solid fuel appliance or that from the higher
storey, must be at least 50 cm higher than the other
it must extend beyond the back flow zone (in Italy,
refer to UNI 10683 point 6.5.8.)
it must allow for maintenance of the chimney
INSTALLATION
EXTERNAL AIR INTAKE
EXTERNAL AIR INTAKE
In general, we suggest two ways to ensure a proper
flow of combustion air.
Air intake without direct connection to the
appliance
Install an intake at floor level with effective area (net of
the mesh or other protective equipment) of at least 80
cm2 (10 cm dia.).
To prevent draughts, we recommend installing the
intake behind the fireplace or behind a radiator.
Installing it in front of the appliance will create
unpleasant draughts.
Air intake with direct connection to the
appliance
Install an air intake of effective area (net of the mesh or
other protective equipment) at least equal to that of the
air intake at the back of the product.
Connect the air intake to the appliance's air intake
with a tube (which may also be flexible).Increase the
diameter of the pipe if it is not smooth: assess its load
loss.
We recommend not exceeding a 1 m length and
curving the tube at most one time, depending on the
draw of the flue.
The air may be drawn from an adjacent room only if:
the flow is taken from permanent and unobstructed
openings communicating with the outdoors;
the adjacent room is never in underpressure
relative to the outdoors;
the adjacent room is not a garage. subject to fire
hazard, a bathroom or bedroom
the adjacent room is not a shared room in the
condominium
In Italy, UNI 10683 provides that ventilation is sufficient
even if a pressure difference between the outdoors
and indoors of no more than 4 PA is guaranteed (UNI
EN 13384-1). The installer who issues the declaration
of conformity is responsible for ensuring these
conditions.
VENTILATION AIR EXCHANGE
VENTILATION AIR EXCHANGE
In addition to the combustion air inlet (which must
draw air from the outside as described above), and
the booster vents, an opening at least 10x10 cm is size
must be made for the ventilation air exchange. This
hole should be made in the cover.
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pellkamin2 12809570

Table of Contents