Filter Change, Second Room; Removing Fan Insert - Maico ER-UP Mounting And Operating Instructions

Recess-mounted exhaust air system according to din 18017-3
Table of Contents

Advertisement

16.2 Filter change, second room

20
6 Protective grille
7 Filter mat
8 Adaptor
Filter change interval every 3 to
6 months, depending on the
amount of dirt.
1. Pull the protective grille [6] forwards.
2. Take out filter mat [7] and replace it.
3. Insert new filter mat into protective grille,
then press protective grille into correct
position on adapter [8] until it audibly
engages.
Filter mats ZRF:
Pack of 5, filter class G2
in accordance with EN 779,
Art. no. 0093.0923
Should you have any questions
Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen
Germany
Tel. +49 7720 694 445
Fax +49 7720 694 175
E-mail: ersatzteilservice@maico.de
16. Cleaning, maintenance

16.3 Removing fan insert

21
11 Fan insert
44 Locking lever
45 Studs [45.1] and [45.2]
1. Switch off mains fuse, secure and fit
warning sign.
2. Open cover [15] and remove.
3. Press locking lever [44] slightly outwards,
( arrow), release and slightly lift the fan
unit [11].
4. Press together locking tabs of stud [45.1]
and raise fan insert slightly.
5. Press together locking tabs of stud [45.2]
and evenly pull entire fan insert out of
bottom part of housing in parallel.
6. Installation is carried out in reverse order.
Degree of protection according to
rating plate only guaranteed if
installed as stipulated (fan insert
engaged, internal cover closed).
39