18. Fault rectification

● Call on the services of a trained electrician
any time there is a fault.
● Repairs should only be carried out by a
trained electrician.
DANGER
Danger to life from electric shock.
 Prior to accessing the connection
terminals, switch off all supply circuits.
Switch off mains fuse, secure against
being accidentally switched back on and
position a visible warning sign.
Fault
Cause, measure
Fan output
● Dirty filter.
inadequate.
Replace filter.
● Locking hook
engaged.
Engage fan insert correctly.
Check diameter of the main
duct, refer to diagram in the
catalogue.
● Supply air cross section
is too small
Increase the supply air
cross section.
VZ, VZ 15,
The power on external
VZC, GVZC
conductor L connected to
EC, F, H
terminal 1 is interrupted
and I models:
when the fan is switched off.
No fan overrun.
Connect the fan as per the
wiring diagram.
Terminals 1 and 3 are
VZ, VZ 15,
reversed.
VZC, GVZC
Connect the fan as per the
EC, I models:
wiring diagram.
Fan starts up
immediately
and stops
immediately if
is switched-off.
Check whether the fan
Fan doesn't
insert is correctly inserted.
start up
not
Incorrect duct diameter.
.
Fault
Cause, measure
Fan is too loud.
● Dirty filter.
Replace filter.
● Fan insert incorrectly
inserted. Insert fan insert
correctly in accordance with
chapter 14.2.
The main duct
Re-calculate pressure
is undersized.
losses.
H model does
The switch-on point has
not switch from
been set too high.
base load to full
Use jumper [S] to set a
load operation
lower switch-on point.
despite there
being moisture
in the room.
H mode no
The switch-off point has
longer switches
been set too low.
back to base
Use jumper [S] to set a
load operation
higher switch-on point. The
or off even after
switch-off point depends on
a long period in
the corresponding switch-on
full load
point.
operation.
Additional
Damage to the unit if
consumers
connected incorrectly.
connected to
Do not connect additional
terminal 4.
consumers to terminal 4.
The unit may only be
connected according to the
wiring diagrams in chap. 22.
GVZC EC:
Check jumper positions,
No start delay /
 chap. 14.2
overrun time
If the fault persists or reoccurs:
Disconnect the fan completely from
the mains power supply. Have error
established and rectified by a trained
electrician.
If you have any questions about
troubleshooting: Service:
+49 7720 6940.
18. Fault rectification
41