Permitted Exhaust Air Systems; Combination Options - Maico ER-UP Mounting And Operating Instructions

Recess-mounted exhaust air system according to din 18017-3
Table of Contents

Advertisement

7. Product information
If the installation deviates from DIN 18017-3:
● ER-UP fans can also be used as
standalone units.
● Installation in the wall or ceiling is
permitted.
● ER-100 fans can be used to extract air
from another room (interior kitchen etc.).

7.3 Permitted exhaust air systems

In accordance with DIN 18017-3, the
following exhaust air systems are permitted
for ER-UP/Centro.
Exhaust air
system
aeroduct fire
protection system
PAM-GLOBAL RML
cast ventilation
system
Ceiling penetration
seal
system
System with
fireproof shaft
Air extraction system
without fire
protection
*
ER-UP/G can be used inside and outside
the shaft, connection duct made from
flexible aluminium duct, second room
connection made from flexible aluminium
duct.
** ER-UPD can be used inside and outside
the shaft, connection duct made from steel
folded spiral-seams duct, second room con-
nection made from flexible aluminium duct.
*** ER-UPB can be used inside the shaft, con-
nection duct made from flexible aluminium
duct, second room connection made from
steel folded spiral-seams duct.
8
UP housing
ER-
ER-
ER-
UP/G
UPD
UPB
No
Yes**
No
No
Yes**
Yes***
Yes*
No
No
Yes**
Yes***
No
Yes*
No
No

7.4 Combination options

The ER recess-mounted exhaust air systems
described here comprise a UP housing and a
fan insert/exhaust air element with cover.
In the shell phase the
ER-UP housing (ER-UP/G, ER-UPD and
ER-UPB) are installed, wired and provided
with a plaster protective cover.
ER-UP/G and ER-UPD housings can be used
with a second room connection set (ER-ZR)
for second room ventilation. Ensure the right
housing variant (ER-UPB/L, ER-UPB/R or
ER-UPB/U) for ER-UPB housings.
WC seat ventilation at the same time as room
ventilation is possible using the second room
connection of the ER-UP/G or ER-UPD
housings. The Maico extraction socket
ER-AS (Ø 70) should be used for this
purpose and a connection established to
the WC seat.
Final assembly is undertaken once the
plastering and paint work is complete.
For decentralised ventilation, an ER 60 or
ER 100 fan insert is placed in the recess-
mounted housing, the exhaust air filter and
cover are fitted.
For centralised ventilation, a Centro-M or
Centro-E exhaust air element is installed with
an exhaust air filter and cover  separate
Centro operating instructions.
ER 100 units are approved for second room
ventilation. The following control types can
be used for this: Standard, VZ, VZ 15, VZC,
G, I, D or RC. Centralised ventilation with
Centro-M or Centro-E exhaust air elements
is possible in combination with ER-UP/G
housings under certain preconditions
 chapter 12.1.1.
ER 60 units are not permitted for the
second room connection.
For ER radio fans and Maico smart
 ER 100 RC instructions.