Carrier 40VAM-C8FATEE Installation Manual page 33

Vrf dx coil interface, dx-coil controller, dx-valve kit, hfc r410a, terminal block with/without relay
Hide thumbs Also See for 40VAM-C8FATEE:

Advertisement

The position of J01 (MCC-1777)
J01
Pulse input
(At factory setting)
Connect
Static input
Cut
Terminal AI1 / AI1: 4 - 20 mA FAN interlocking control by external input
• FAN mode is switched by external 4 - 20 mA input.
• Both FAN control with 4 - 20 mA input and FAN mode change with remote controller are valid, but boost priority is
given.
• The FAN priority control is switched by the DN setting of [4A0].
• 0000: Default (no change in FAN mode by 4 - 20 mA input)
• 0001: FAN control by 4 - 20 mA input, but priority is given to FAN control from the outdoor unit
• 0002: FAN control 4 - 20 mA input with priority
• The FAN mode switching threshold value for 4 - 20 mA input can be changed in the DN setting (See the table as
below).
* Terminal AI2 / AI2 cannot be used.
* The change in FAN speed with 4 - 20 mA input is also reflected in the 0 - 10 V output of AO1 / AO1.
mA
HH
18
H
14
L
7
40VAM--C8FATEE
(Terminal block without relay)
MAX. 100 m
Al1
(Input
4 - 20 mA)
AI1
Action
ON
Pulse width 200 to 300 ms
Pulse interval 200 to 300 ms or more.
ON
[DN]
Default
17
[4A2]
0004 (4 mA)
[4A1]
0013 (13 mA)
13
[4A3]
0007 (7 mA)
6
* 1: Upper limit. DN [4A1] + DN [4A2] ≤ 18 mA
* 2: Lower limit. DN [4A1] - DN [4A3] ≥ 4 mA
Locally procured
4 - 20 mA Signal (+)
GND (-)
OFF
OFF
Details
[4A1] +4 mA
Applicable range +1 to +11 *¹
Applicable range 7 mA to 16 mA
[4A1] -7 mA
Applicable range -1 to -12 *²
40VAMR-C8FATEE
(Terminal block with relay)
– 32 –
Same as on the left