Terminal DI1 / DI1: Safety contact (Normal close)
MODE 1 (Normally close, DC12 V) *When Bit1 of SW505 is OFF
• If this contact is open for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off
automatically.
MODE 2 (Normally open, DC12 V) *When Bit1 of SW505 is ON
• If this contact is short for more than 1 minute, the check code P10 is generated and the Dx-coil controller switches off
automatically.
SW701
OFF
ON
1
GND
DI1
SIGNAL (12 V)
DI1
SW701
OFF
ON
1
GND
DI1
SIGNAL (12 V)
DI1
SW701
SW505
OFF
OFF
ON
OFF
ON
ON
SW505
ON
OFF
1 2 3 4
MAX. 100 m
Locally procured
Normally closed
SW505
ON
OFF
1 2 3 4
MAX. 100 m
Locally procured
Normally open
The coil drive voltage is input to the relay arranged locally for DI1, and judge that the close is
positive. (Default)
Relay: Local arrangement
The coil drive voltage is not input to the relay arranged locally for DI1, and judge that the open is
positive.
Relay: Local arrangement
For DI1, short-circuit the (+) signal voltage and DI1 (-) GND with a SW or harness, and judge that
the close is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
For DI1, open the (+) signal voltage and DI1 (-) GND, and judge that the open is positive.
Relay: Not required
* The signal voltage is DC12 V ± 10%, and it is necessary to add a SW element to the signal line.
SW701
Bit1:
OFF
ON
OFF
1
SIGNAL (+)
SIGNAL (-)
SW701
Bit1:
OFF
ON
ON
1
SIGNAL (+)
SIGNAL (-)
Function
– 30 –
SW505
SW505
ON
OFF
1 2 3 4
MAX. 100 m
Locally procured
Signal Voltage (DC12 V ± 10%)
DI1
GND
DI1
Normally closed
SW505
ON
OFF
1 2 3 4
MAX. 100 m
Locally procured
Signal Voltage (DC12 V ± 10%)
DI1
DI1
GND
DI1
Normally open
Bit1:
OFF
(+)
(-)
Bit1:
ON
(+)
(-)