Download Print this page

Carrier 40VAM-C8FATEE Installation Manual page 27

Vrf dx coil interface, dx-coil controller, dx-valve kit, hfc r410a, terminal block with/without relay
Hide thumbs Also See for 40VAM-C8FATEE:

Advertisement

Terminal
DO1
Operating output
DO2
Alarm active digital output
DO3
Fan motor active digital output
DO4
Defrost mode digital output
DO5
DO1 Digital output 1 (User defined)
DO6
DO2 Digital output 2 (User defined)
DO7
Thermostat ON digital output
DO8
Cooling / heating start up control signal output
DO9
Pre defrost signal output
DOA
Cooling OPEN / heating CLOSE output
DOB
Notice code output
DOC
Fan high speed output
DOD
Fan medium speed output
DOE
Fan low speed output
N1
Blank
N2
Blank
DI1
Safety (Normal close)
DI2
External trouble input
DI3
Forced thermostat OFF input
DI4
Notice code input
DI5
Operation mode input (cool / heat)
DI6
External ON / OFF input
AI1
Input 1 (4-20 mA)
AI2
Input 2 (4-20 mA)
AI3
Input 1 (0-10 V)
AI4
Input 2 (0-10 V)
AO1
Output 1 (0-10 V)
AO2
Output 2 (0-10 V)
R, BL, OR, Y, W PMV 1 / PMV 2
MdG
Modbus G
MdA / MdB
Modbus A / Modbus B
Terminal L(1) / N(2) / (3): Power Supply Input
• Dx-coil controller should be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm. If the outdoor unit is a VRF model, connect it to L(1) / N(2).
Terminal Uv(U1) / Uv(U2): Communication line (Dx-coil controller and outdoor units)
• Details regarding the wiring can be found in the Installation Manual of the VRF outdoor unit.
Terminal AB / AB: Remote controller Wiring
• At these terminals an optional wired remote controller can be attached.
(Useful for installation, maintenance and Group control)
Function
Outdoor unit
Uv(U1) / Uv(U2)
Dx-coil controller
AB / AB
Remote controller
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
Digital output
none
none
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Analog input
Analog input
Analog input
Analog input
Analog output
Analog output
-
-
-
– 26 –
Description
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
DC12 V
-
-
DC12 V or No voltage
DC12 V or No voltage
DC12 V or No voltage
DC12 V or No voltage
DC12 V or No voltage
DC5 V
4 - 20 mA
4 - 20 mA
0 - 10 V
0 - 10 V
0 - 10 V
0 - 10 V
R: DC12 V
-
-