Carrier 40VAM-C8FATEE Installation Manual page 32

Vrf dx coil interface, dx-coil controller, dx-valve kit, hfc r410a, terminal block with/without relay
Hide thumbs Also See for 40VAM-C8FATEE:

Advertisement

Terminal DI2 / DI2: External trouble Input
• An AHU fan operation monitor (Field supply), could be attached at this dry contact terminal (For example, the
abnormality of the fan motor). A closed contact generates the check code L30.
Terminal DI3 / DI3: Forced thermostat OFF Input
• When signal input, AHU is in "thermostat-off" status forcibly.
Terminal DI4 / DI4: Notice code Input
• If there is input, a spanner mark will be displayed on the remote controller. The system will not stop.
Check "DN settings" for the setting method.
Terminal DI5 / DI5: Operation Mode Input (Cool / Heat)
• Cool / Heat mode selection over a dry contact.
If the contact is short-circuited, system changes to heat mode.If the contact is open, system changes to cool mode.
• Only cool mode and heat mode are available.
Function
Mode Input Cool / Heat
When Bit4 of SW502 is turned on in DDC type, capacity demand can be achieved by short-circuiting Terminals DI2 to
DI4.
Short - circuit
DI2 - DI2
DI3 - DI3
DI4 - DI4
* If all are short-circuited, the DI3 function has priority.
When SW701 is ON (no voltage), apply a voltage of DC12 V ± 10% and wiring as follows.
MAX. 100 m
SIGNAL (+)
DI2 -    DI4
SIGNAL (-)
DI2 - DI4
Terminal DI6 / DI6: External ON/OFF Input
• When using with DDC, it starts by turning on this terminal.
40VAM--C8FATEE
(Terminal block without relay)
DI6
Input
DC5 V
DI6
Terminal
DI5 / DI5
Cooling step
2
5
11
Locally procured
Signal Voltage (DC12 V ± 10%)
GND
Normally open
MAX. 100 m
Locally procured
Relay coil signal
Function
COOL mode active
Heating step
3
9
13
(+)
(-)
(Terminal block with relay)
– 31 –
SHORT
HEAT mode active
40VAMR-C8FATEE
Same as on the left