Remove and Replace a Power Supply

Figure 33: Remove the Drive Tray
3
Drive tray screws ( two on each side)
Step 3
Install a new drive:
a) Place a new drive in the empty drive tray and install the four drive-tray screws.
b) With the ejector lever on the drive tray open, insert the drive tray into the empty drive bay.
c) Push the tray into the slot until it touches the backplane, and then close the ejector lever to lock the drive in place.
Remove and Replace a Power Supply
The Private Cloud appliance ships with two power supplies, which are redundant and hot-swappable. One is
the active power supply and the other is the standby power supply (1+1).
The Private Cloud appliance also supports cold redundancy. Depending on the power being drawn by the
Private Cloud appliance, one power supply might actively provide all power to the system while the remaining
power supply is put into a standby state. For example, if the power consumption can be satisfied by power
supply 1, then power supply 2 is put into a standby state.
Caution
Cisco Secure Endpoint PC4000 Hardware Installation Guide
38
When you replace power supplies, do not mix power supply types in the Private Cloud appliance. Both power
supplies must be the same wattage and Cisco PID.
4
Drive removed from drive tray
Maintenance and Upgrade