ERROR CODES
Error states are produced when UPS detects a critical problem that avoids its normal operation in ONLINE mode. This condition is
described by steady symbol and code on LCD. A continuous beep is also generated by the UPS.
FAILURE
BUS START FAIL
BUS OVER
BUS UNDER
INVERTER SOFT START FAIL
INVERTER VOLTAGE HIGH
INVERTER VOLTAGE LOW
INVERTER OUTPUT SHORT
BATT VOLTAGE TOO HIGH
BATT VOLTAGE TOO LOW
CHARGER OUTPUT SHORT
OVER TEMPERATURE
OUTPUT OVERLOAD
CHARGER FAILURE
OVER INPUT CURRENT
AUDIBLE ALARM BEEPS
ERROR:
BATTERY MODE:
BYPASS MODE:
LOW BATTERY:
www.xmart-ups.com
USER MANUAL - OPTIMA T10 1K/1.5K/2K/3K
Continuous Beep
1 "Beep" every 5s
1 "Beep" every 10s. This alarm cannot be muted
1 "Beep" every 2s. This alarm cannot be muted
VER.2310.26-One (ENG)
CODE
01
02
03
11
12
13
14
27
28
2A
41
43
45
49
ICON
18