Our monitoring software allows user to manage UPS and monitoring of all its features.
Main software features are: Configuring UPS parameters, Automatic shutdown for protected PCs (OS and files) when long blackouts
force UPS to power-off, Scheduled battery tests, shutdown and start-up and Easy interface for monitoring UPS and Main service.
CD software is usually included inside the box. For some models, software can be downloaded from our website. Software manual can
be downloaded from our website also.

11. BATTERIES: CARE AND REPLACEMENT

To have a longer Battery life, it is recommended to apply a deep discharge to batteries every 3 months. It is also recommendable to
operate UPS with a room temperature below 25ºC. Operating UPS with higher room temperatures will short dramatically battery life.
IMPORTANT: RECHARGING PLAN FOR LONG STORAGE
If UPS will be stored for long time, it is mandatory to recharge UPS periodically. If UPS is not recharged according to this plan, batteries
will get permanent damage. This kind of damage is not covered by warranty.
Recharging plan is conditioned to storage temperature:
STORAGE TEMPERATURE: - 25ºC to + 30ºC : RECHARGE EVERY 4 MONTHS / RECHARGE DURING 6 HOURS
STORAGE TEMPERATURE: + 30ºC to + 45ºC : RECHARGE EVERY 2 MONTHS / RECHARGE DURING 6 HOURS
BATTERY REPLACEMENT
Batteries must be replaced by technical personnel only.
Batteries are located inside the UPS cabinet. For having access to batteries, UPS must be turned off and disconnected from AC
source. Top cover of the UPS must be separated from main case body by removing screws.
Batteries must be replaced by new batteries with same specifications and technology.
WARNING - BATTERIES:
Batteries must be disposed according to your country regulations.
Do not dispose batteries in fire as they might explode
Do not try to open batteries, there are dangerous liquids inside.