Sia Quick Reference Guide - Honeywell L5210 Series Installation And Setup Manual

Hide thumbs Also See for L5210 Series:
Table of Contents

Advertisement

Programming Section
Installation and Setup Guide or Programming Guide
Reporter/
Exit Error
Report Selection
Recent Closing
Alarm Cancel
Reporter/Options
Call Wait Cancel
Number of Reports
Alarm Report Delay
(Abort Window)
System Settings
Entry Delay # 1
Entry Delay # 2
Exit Delay
Restart Exit Time
Exit Warning
Auto Stay Arming
Cross Zone Delay
Zones
Fire Alarms
User Guide
User Functions/
Duress
User Access
System Functions/
System Test
Testing the System**
Communications
* Combined Entry Delay and Alarm Report Delay (Abort Window) should not exceed 1 minute.
** Refer to the User Guide for procedures on Testing the System.
Note: Using the Call Waiting Cancel feature on a non-Call Waiting line will prevent successful communication to the Central Station.
Feature
Range
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
1 to 6 Reports
15, 30 and 45 seconds
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or 4
minutes
None, 15, 30, 45, 60 and
90 seconds and 2, 3 or 4
minutes
45, 60, 90 seconds and 2
minutes
Enabled or Disabled
Not selectable
Enabled or Disabled
30 seconds and 2 minutes
(in 30 second increments),
3 minutes and 4 minutes
Zone Type "Fire with
Verification" must be
selected for Fire Zone 95
Duress Code is
Programmed by Master
User as User 16
System tests provided as a
User Function
While the system is in Test
mode, no alarm reports are
sent to the Central Station
LYNX Touch Installation and Setup Guide

SIA Quick Reference Guide

Shipping Default
Enabled
Enabled
Enabled
Field is blank (a PBX prefix
is entered to enable)
2 Reports
30 Seconds
30 Seconds
30 Seconds
60 Seconds
Yes (Enabled)
Always enabled
Yes (Enabled)
None (Disabled)
Disabled
Disabled
n/a
Disabled
- 81 -
SIA Requirement
Enabled
Enabled
Enabled
Enabled if User has call
waiting
2 Reports
30 Seconds*
30 Seconds minimum
30 Seconds minimum
45 seconds minimum
Enabled
Enabled
Enabled
Enabled and two zones
programmed
Disabled
Disabled
n/a
Disabled