Instantaneous Failure; U2" Outdoor Unit: Power Supply Insufficient Or - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Si34-601A
3.42 "U2" Outdoor Unit:

Instantaneous Failure

U2
Remote
Controller
Display
Applicable
RXYQ5P~54P
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
current-limiting voltage does not reach 200V or more or exceeds 740V.
Decision
Conditions
Supposed
Causes
Troubleshooting
Power Supply Insufficient or
Power supply insufficient
Instantaneous power failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect
Faulty compressor
Faulty fan motor
Faulty connection of signal cable
Troubleshooting by Indication on the Remote Controller