Refrigerant Circuit; Rxyq5P - Daikin VRV III RXYQ5-54PY1 Service Manual

R-410a heat pump 50hz
Table of Contents

Advertisement

Refrigerant Circuit

1.

Refrigerant Circuit

1.1

RXYQ5P

No. in
refrigerant
Symbol
system
diagram
A
M1C
Inverter compressor (INV)
D
M1F
Inverter fan
Electronic expansion valve
E
Y1E
(Main: EV1)
G
Y1S
Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
J
Y2S
Solenoid valve (Oil return: SVO) Used to return oil from the accumulator to the compressor.
Solenoid valve (Injection) SVT Used to cool the compressor by injecting refrigerant when the compressor discharge
K
Y4S
M
Y3S
4-way valve
N
S1NPH High pressure sensor
O
S1NPL Low pressure sensor
HP pressure switch (For INV
P
S1PH
compressor)
T
Pressure regulating valve 1
W
Capillary tube
1
R1T
Thermistor (Outdoor air: Ta)
2
R2T
Thermistor (Suction pipe: Ts)
Thermistor (INV discharge
3
R3T
pipe: Tdi)
Thermistor (Heat exchanger
4
R4T
deicer: Tb)
5
R6T
Thermistor (Liquid pipe Tl)
Thermistor (Accumulator inlet
6
R7T
Ts1)
60
Name
Inverter compressor is operated on frequencies between 52Hz and 188Hz by using
the inverter. The number of operating steps is as follows when Inverter compressor is
operated.
RXYQ5P : 18 steps
Since the system is of air heat exchanging type, the fan is operated at 9-step rotation
speed by using the inverter.
While in heating operation, PI control is applied to keep the outlet superheated degree
of air heat exchanger constant.
temperature is high.
Used to switch the operation mode between cooling and heating.
Used to detect high pressure.
Used to detect low pressure.
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the compressor
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
resulting in no damage of functional parts due to the increase of pressure in
transportation or storage.
Used to return the refrigerating oil separated through the oil separator to the
compressor.
Used to detect outdoor temperature, correct discharge pipe temperature, and others.
Used to detect suction pipe temperature.
Used to detect discharge pipe temperature, make the temperature protection control of
compressor, and others.
Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
operation, and others.
Used to detect liquid pipe temperature.
Used to detect gas pipe temperature at the accumulator inlet. Keep the suction
superheated degree constant in heating operation, and others.
Major Function
Si34-601A
Refirgerant Circuit