Field Setting
3.1.2 Wireless Remote Controller - Indoor Unit
BRC7C type
BRC7E type
BRC4C type
1. When in the normal mode, push the "
2. Select the desired "mode No." with the "
3. Pushing the "
4. Pushing the "
5. Push the timer "
6. Push the "
(Example)
When setting the filter sign time to "Filter Dirtiness-High" in all group unit setting, set the Mode
No. to "10", Mode setting No. to "0" and setting position No. to "02".
162
then enters the "field set mode."
" button, select the first code No.
" button, select the second code No.
" button and check the settings.
" button to return to the normal mode.
" button for 4 seconds or more, and operation
" button.
Si34-601A
Test Operation