Daikin VRV III RXYQ5-54PY1 Service Manual page 189

R-410a heat pump 50hz
Table of Contents

Advertisement

Field Setting
The following settings are made by pushbutton switches on PC board.
In case of multi-outdoor unit system, various items should be set with the master unit.
(Setting with the slave unit is disabled.)
The master unit and slave unit can be discriminated with the LED display as shown below.
LED display
Outdoor-
There are the following three setting modes.
Initial status (when normal) : Used to select the cool/heat setting. Also indicates during
"abnormal", "low noise control" and "demand control".
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Used to check the program made in Setting mode 2.
Press BS1 (MODE button) for more than 5 sec.
Setting mode 2
Setting item selection
(SET button)
Setting condition
selection (SET button)
Setting condition
(Contents) display
178
Setting by pushbutton switches
MODE
H1P
Single-outdoor-unit
7
system
7
Master
7
Slave 1
multi
system
7
Slave 2
Setting mode 1 (H1P off)
Setting mode 2 (H1P on)
Monitor mode (H1P blinks)
Mode changing procedure 1
Using the MODE button, the modes can be changed as follows.
Push and hold the BS1
(MODE button) for 5 seconds.
Setting mode 2
Push the BS1(MODE button) one time.
MODE
On
H1P
Mode changing procedure 2
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS3
(RETURN button).
Press BS1
(MODE button).
COOL/HEAT select
TEST
IND
MASTER
H2P
H3P
H4P
7
8
7
7
8
7
7
7
7
7
7
7
BS1
BS2
BS3
BS4
MODE
SET
RETURN
TEST
(Normal)
Setting mode 1
MODE
Off
H1P
(Set): Select mode with BS2 (SET button) in each selection step.
Setting mode 1
Press BS1(MODE button).
(Initial condition)
Low
Demand
noise
SLAVE
H5P
H6P
H7P
7
7
7
7
7
7
7
7
7
7
7
7
(Factory setting)
BS5
RESET
(V2760)
Push the BS1(MODE button)
one time.
Monitor mode
MODE
H1P
Monitor mode
Check item selection
(SET button)
Press BS3
(RETURN button).
Contents display
Press BS3
(RETURN button).
Press BS1
(MODE button).
(V2762)
Test Operation
Si34-601A
Multi;
H8P
7
8
9
7
Blinking
(V2761)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iii si34 601a rxyq py1

Table of Contents