Daikin VRV III RXYQ5-54PY1 Service Manual page 57

R-410a heat pump 50hz
Table of Contents

Advertisement

Specifications
Ceiling Mounted Built-in Type
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number of
Units
Fan
Air Flow Rate (H/L)
4 External static
pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Model
Decoration
Panel Color
Panel
Dimensions: (H×W×D)
(Option)
Weight
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 External static pressure is changeable to change over the connectors inside electrical box, this pressure
5 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
6 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
46
FXSQ40MVE
kcal/h
4,000
Btu/h
16,000
kW
4.7
kW
4.5
kcal/h
4,300
Btu/h
17,100
kW
5.0
Galvanized Steel Plate
mm
300×700×800
mm
3×14×1.75
0.132
D18H2A
Sirocco Fan
W
65×1
m³/min
11.5/9
Pa
88-49-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP25
mm
(External Dia. 32 Internal Dia. 25)
kg
30
dBA
38/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS45DJW1
White (10Y9/0.5)
mm
55×800×500
kg
3.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
means
"High static pressure-Standard -Low static pressure".
values are normally somewhat higher during actual operation as a result of ambient conditions.
FXSQ50MVE
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
300×700×800
3×14×1.75
0.132
D18H2A
Sirocco Fan
85×1
15/11
88-59-29
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
31
41/36
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS45DJW1
White (10Y9/0.5)
55×800×500
3.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
3D039431
Si34-601A
FXSQ63MVE
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
300×1,000×800
3×14×1.75
0.221
2D18H2A
Sirocco Fan
125×1
21/15.5
88-49-20
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Glass Fiber
Resin Net (with Mold Resistant)
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP25
(External Dia. 32 Internal Dia. 25)
41
42/35
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A P Series
BYBS71DJW1
White (10Y9/0.5)
55×1,100×500
4.5
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation
for Fitting, Sealing Pads, Clamps,
Screws, Washers.
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Specifications

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv iii si34 601a rxyq py1

Table of Contents