Daikin VRV III RXYQ5-54PY1 Service Manual page 52

R-410a heat pump 50hz
Table of Contents

Advertisement

Si34-601A
Slim Ceiling Mounted Duct Type (with Drain Pump)
Model
1 Cooling Capacity (19.5°CWB)
2 Cooling Capacity (19.0°CWB)
3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
6 Sound Level (H/L)
Safety Devices
Refrigerant Control
Standard Accessories
Drawing No.
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m, level
3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 External static pressure is changeable to set by the remote controller this pressure means "High static
6 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
Specifications
FXDQ40NAVE
kcal/h
4,000
Btu/h
16,000
kW
4.7
kW
4.5
kcal/h
4,300
Btu/h
17,100
kW
5.0
Galvanized Steel Plate
mm
200×900×620
mm
3×12×1.5
0.176
Sirocco Fan
W
62×1
m³/min
10.5/8.5
Pa
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
mm
6.4 (Flare Connection)
φ
mm
12.7 (Flare Connection)
VP20
mm
(External Dia. 26 Internal Dia. 20)
kg
27
dBA
34/30
Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
difference: 0m.
difference: 0m.
0m. (Heat pump only)
pressure - Standard static pressure".
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
FXDQ50NAVE
5,000
19,800
5.8
5.6
5,400
21,500
6.3
Galvanized Steel Plate
200×900×620
3×12×1.5
0.176
Sirocco Fan
130×1
12.5/10.0
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
6.4 (Flare Connection)
φ
12.7 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
28
35/31
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
3D051253
Specifications
FXDQ63NAVE
6,300
24,900
7.3
7.1
6,900
27,300
8.0
Galvanized Steel Plate
200×1100×620
3×12×1.5
0.227
Sirocco Fan
130×1
16.5/13.0
44-15
5
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal / Washable / Mildew Proof
φ
9.5 (Flare Connection)
φ
15.9 (Flare Connection)
VP20
(External Dia. 26 Internal Dia. 20)
31
36/32
Electronic Expansion Valve
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3