Si34-601A
4.
Troubleshooting (OP: Central Remote Controller)
"M1"
4.1
PC Board Defect
M1
Remote
Controller
Display
Applicable
Central remote controller
Schedule timer
Models
Method of
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Detection
Malfunction
When + polarity and - polarity are detected at the same time.
Decision
Conditions
Supposed
Causes
Troubleshooting
Replace the central remote controller.
Troubleshooting
Defect of central remote controller PC board
Defect of Schedule timer PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Turn ON the power supply of
the central equipment
with M1 displayed once again.
Is the M1 displayed again?
Without M1 displayed
Troubleshooting (OP: Central Remote Controller)
With M1 displayed
Replace the central
equipment.
Central equipment: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
297