EtherCAT
7.3.1

Operation with EtherCAT factory setting

If the data transmission path is operated with the factory setting, the device with "Frequency F4" must be
installed on the master side. Device with "Frequency F3" must be installed on the slave side. A sticky note
is attached to the devices for this purpose.
Fig. 7.3:
Sticky note
E therC A T
1
1
Master
2
Bus terminals
3
Master-side installation
4
Slave-side installation
5
Device with "Frequency F4"
Fig. 7.4:
Device with "Frequency F4" installed on master side (factory setting)
MAS EtherCAT configuration activated on slave side!
If the MAS EtherCAT configuration is incorrectly activated on the slave side, it may result in an
overflow of the Lost Frames counter of the EtherCAT control.
With the overflow of the Lost Frames counter, all network communication on the EtherCAT mas-
ter side is deactivated.
Ä All sensors and actuators that are operated on the affected EtherCAT master can no longer
be controlled.
Ä In the case of moving machine or system parts, an emergency stop can result in property
damage and personal injury.
Ä Leuze electronic GmbH + Co. KG accepts no liability if the installation and mounting regula-
tions are not observed.
Leuze electronic GmbH + Co. KG
2
3
D D LS 538
F requency F 4
„M A S " = on
WARNING
5
4
D D LS 538
I/O 's
F requency F 3
„M A S " = off
DDLS 538 ... S2 ...
53