11.6 Control System 7 Day Timeout

If you have your Proflame 2 system set to CPI
(continuous pilot ignition) with 7 consecutive days
without ignition of the main burner, the pilot will turn
off. This a standard safety feature of the SIT Proflame
2 system.
Once you turn CPI on, the 7 day timer will start. If at
any time during the following 7 days your main burn-
er ignites, it will reset the timer back to 7 days.
See section 11.9.3 PILOT IGNITION SELECTION (page
55) for more information.
How to check if your system is set to CPI:
The LCD screen will display the snowflake icon.
To select the preferred pilot ignition feature,
1. With the system in the OFF position, press the mode
key to index the CPI mode icon.
2. Press the up arrow key to activate CPI.
3.
Press the down arrow key to return to IPI. A single
'beep' will confirm reception of the command.
To Turn ON the appliance
1.
With the system in the OFF position, press the remote
control ON/OFF key to turn ON the appliance.
A single 'beep' will emit from the IFC module to con-
firm reception of the command.
The LCD screen will display all active icons, and the IFC
module will start the ignition sequence.

11.7 IFC Module Ignition Sequence

The IFC module will try (2) times for ignition, each lasting
approximately (60) seconds, with approximately (35) sec-
onds between each attempt.
1.
With the system in OFF position, press the remote
control ON/OFF key. Approximately (4) seconds after
this key is depressed, the IFC module will generate
sparks to the pilot hood.
2.
First ignition attempt will generate sparks for (60)
seconds.
3.
If there is no flame ignition (rectification) within the
(60) second time frame, the IFC module will stop gen-
erating sparks for approximately (35) seconds.
4.
After (35) seconds of wait time, the IFC module will
generate sparks for another (60) seconds for the sec-
ond ignition attempt.
5.
If there is no positive rectification after (60) seconds,
the IFC module will go into a lock out. The red LED will
blink (3) times, in intervals, until the system is reset.
11.7.1 Reset IFC Module after Lockout
11.7.1.1 ON/OFF Rocker Switch
1.
Set the ON/OFF rocker switch to the OFF position.
2.
After approximately (2) seconds, move the switch to
the ON position. The ignition sequence will start
again.
Hussong Mfg. Co, Inc.
NDK-36-DV - PFS Report No. 23-152
11.7.1.2 Remote Control ON/OFF Key
1. Press the remote control ON/OFF key to turn the sys-
tem OFF.
2. After approximately (2) seconds, press the ON/OFF
key again. The ignition sequence will start again.
11.7.1.3 Cycling Flame
1. Press the remote control down arrow key during
flame adjustment mode to reduce the flame to OFF
(indicated by OFF displayed on the LCD screen).
2. After approximately (2) seconds, press the up arrow
key. The ignition sequence will start again.

11.8 Additional Diagnostic Information

Low Battery Condition (<4V) Remote Control:
Battery Icon will appear on LCD remote control dis-
play.
Replace batteries.
Low Battery Condition (<4V) Battery Backup:
The red LED Indicator will blink (1) time in intervals.
A low double-beep emits from the IFC control module
when it receives an ON/OFF command from the re-
mote control.
Replace Batteries.
Pilot Flame Error Condition:
Red LED Indicator will blink (2) times in intervals. Con-
tact your dealer if this occurs.
System Lock Out Condition:
Red LED Indicator will blink (3) times in intervals.
Verify gas is turned on.
Verify sensor is not shorted.
Follow section 11.2, INITIALIZE THE CONTROL SYSTEM
on page 52.
56
Starting Serial Number: 23 N36DV00001 38
Rev. 1 - July 2023