14. Technical Information

Measurement process:
Range:
Media:
Minimum conductivity:
Max. medium viscosity:
Max. pressure:
Accuracy:
Repeatability:
Response time flow t
(alarm/pulse/frequency output):
(analogue output):
Temperature measurement
Sensor:
Accuracy:
Measuring range:
Response time of temperature t 90
(signal output):
Mounting position:
In-/outlet:
Pressure drop (max at ME)
Handling:
Housing:
Wetted parts
Connection fitting and housing:
Insulation parts:
Elektrodes:
Seals:
Protection:
Media temperature:
Ambient temperature:
A5E48762204-AA
electromagnetic
see order details
conductive fluids
≥20 µS/cm
70 mm 2 /s
16 bar
<±(0.8% of reading+ 0.5% of full scale)*
±0.2% of full scale
90
<100 ms
<1 s
PT1000
≤±2 °C (flow >0.2 m/s)
temperature range of medium
<20 s
in all directions
3 x DN/2 x DN
MB 05
MB 10
MB 15
MB 20
MB 40 450 mbar
MB 35 120 mbar
4 optical touch fields, useable with hand gloves
stainless steel 1.4404,
display screen PMMA
stainless steel 1.4404
PEEK
stainless steel 1.4404
FKM: MIM-12xxx; EPDM: MIM-13xxx
IP 67
-20 °C ... +70 °C
-20 °C ... +85 °C (separate version PVC cable)
-20 °C ... +130 °C (separate version ETFE cable)
-20 °C ... +60 °C (compact version and display
for remote version)
-20 °C...+130 °C (sensor for remote version
with ETFE cable)
-20 °C...+85 °C (sensor for remote version
with PVC cable)
SITRANS FM100
400 mbar
50 mbar
250 mbar (3/4 "), 30 mbar (1")
80 mbar
page 47