Cover Jam Screw - Emerson Rosemount 8732 Quick Installation Manual

Magnetic flowmeter system
Table of Contents

Advertisement

Quick Installation Guide
00825-0100-4662, Rev CD
Rosemount 8732
June 2013
S
6
...
TEP
CONTINUED
8732E Power Supply
For AC power applications (90-250 VAC, 50-60 Hz) connect AC Neutral to terminal 9 (AC N/L2)
and connect AC Line to terminal 10 (AC/L1). For DC power applications connect negative to
terminal 9 (DC -) and positive to terminal 10 (DC +). Units powered by 12-42 V DC power supply
may draw up to 1 amp of current. See Figure 22 for terminal block connections.
Figure 22. 8732E Transmitter power connections

Cover Jam Screw

For transmitter housings shipped with a cover jam screw, the screw should be properly installed
once the transmitter has been wired and powered up. Follow these steps to install the cover jam
screw:
1. Verify that the cover jam screw is completely threaded into the housing.
2. Install the transmitter housing cover and verify that the cover is tight against the housing.
3. Using an M4 hex wrench, loosen the jam screw until it contacts the transmitter cover.
1
4. Turn the jam screw an additional
/
turn counterclockwise to secure the cover.
2
(Note: Application of excessive torque may strip the threads.)
5. Verify that the cover cannot be removed.