10 - MANAGEMENT OF THE ANALOGUE INPUTS
When reading the operation parameters for the pressure levels while the machine is on, the sensors can be adjusted with the OK
button if there is a difference between a value that is read and the corresponding value measured by a pressure gauge.
Exemple :
P 3 x x H P x
Press OK to access and change the adjustment value.
S E N S O R
Press OK to confirm the new adjustment value and go back to the operation parameter.
Press ESC to cancel any changes made and go back to the operation parameter.
This readjustment will be used to correct the difference between the value measured by a pressure sensor and the value read on a
pressure gauge.
The resulting new slope will then be used for control.
68
P R E S S U R E
x x . x b
A D J U S T M E N T
x x . x b
H P x
0 . 0 b
[- 1 + 2.5] 0 by default