6 - LIST OF PARAMETERS
No.
Description
1
437 State of recovery heat trace cable control output On/Off
1
438 State of maximum power output
1
439 State of boiler output
1
440 State of cooling/heating output
1
441 State of HP control output, stage 1, circuit 1
1
442 State of HP control output, stage 2, circuit 1
1
443 State of HP control output, stage 1, circuit 2
1
444 State of HP control output, stage 2, circuit 2
State of HP control output, stage 3, circuit 1 or
1
445
State of HP control output, common stage 1
State of HP control output, stage 3, circuit 2 or
1
446
State of HP control output, common stage 3
1
447 Driving voltage, stage 1, HP control
1
448 Driving voltage, stage 1, circuit 1, HP control
1
449 Driving voltage, stage 1, circuit 2, HP control
1
450 Driving voltage, common stage 1, HP control
1
451 State of circuit 1 balance valve output
1
452 State of circuit 2 balance valve output
1
530 State of electric stage 1
1
531 State of electric stage 2
1
532 State of electric stage 3
1
533 State of electric stage 4
1
535 Air blade percentage information
1
555 CPU version number
1
556 Console version number
1
557 Version number of circuit 2 board
1
558 Version number of changeover board
1
559 Version number of auxiliary heater board
1
560 Version number of circuit 1 expansion valve
1
561 Version number of circuit 2 expansion valve
1
570 "SO" order number"
1
571 MO number
1
572 Machine identification name 
1
573 Machine identification number 
Circuit 1
3
601 Circuit 1 valve type
3
602 Circuit 1 superheat setpoint
3
603 Circuit 1 MOP point
3
604 Circuit 1 MOP value
605 Opening of C1 valve when air conditioning
3
started
3
606 Opening of C1 valve when heat pump started
3
607 Opening time at start-up, C1
3
608 Circuit 1 slow mode
Circuit 2
3
611 Circuit 2 valve type
3
612 Circuit 2 superheat setpoint
3
613 Circuit 2 MOP point
3
614 Circuit 2 MOP value
615 Opening of C2 valve when air conditioning
3
started
Setting
Outputs (continued)
On/Off
On/Off
On/Off
On/Off if P21 = without
High Temperature mode/Low
Noise mode/Off if P191 =
acoustic
On/Off
On/Off
On/Off
On/Off
On/Off
0-10 V
0-10 V
0-10 V
0-10 V
On/Off
On/Off
On/Off
On/Off
On/Off
On/Off
0-100 %
*
XX.YY VCM XX.YY
XX.YY VCM XX.YY
Electronic Expansion Valve
EX4 - EX5 - EX6 - EX7 - EX8
0,5 to 30°C
Yes - No
+ 5 to 25°C
10 to 100 %
10 to 100 %
1 to 60 seconds
Yes/No
EX4 - EX5 - EX6 - EX7 - EX8
0,5 to 30°C
Yes - No
+ 5 to 25°C
10 to 100 %
Default
Display conditions
If P2 ≠ 1 (water-to-water) and P29,1 = Yes
If P111 = Max. power
If P111 = Boiler
If P111 = Cooling/Heating
If P21 = without, P2 = 2, 3
If P180 = 2 and P3 = 1,
P2 = 2, 3
If P180 = 1 and P3 = 2,
P2 = 2, 3
If P180 = 2 and P3 = 2,
P2 = 2, 3
If P180 = 3 and P3 = 2, P11 = split, P2
= 2, 3 or
If P180 = 3 and P3 = 2, P11 = mixed
If P180 = 3 and P3 = 2, P11 = split, P2
= 2, 3 or
If P180 = 3 and P3 = 2, P11 = mixed
If P21 = 2 or 3 and P11 = Intertwined
If P21 = 2 or 3 and P11 = split or mixed
If P21 = 2 or 3 and P11 = split or mixed
If P21 = 2 or 3 and P11 = Mixed
If P12 = Yes
If P12 = Yes
If P22 = Yes
If P22 = Yes
If P22 = Yes
If P22 = Yes and P112 = 4
If P20 =Yes and P10 = Centrifugal
If P3 = 2
If P2 = reversible air-to-water
If P22 = Yes
If P42 = VCM and P3 = 1
If P42 = VCM and P3 = 2
To be entered via a PC
To be entered via a PC
To be entered via a PC
To be entered via a PC
EX4
If P42 = VCM and P3 = 2
6
If P42 = VCM and P3 = 1
No
If P42 = VCM and P3 = 1
15
If P42 = VCM, P603 = Yes and P3 = 1
50
If P42 = VCM and P3 = 1
If P42 = VCM and P3 = 1
20
and P2 = reversible air-to-water
5
If P42 = VCM and P3 = 1
No
If P42 = VCM and P3 = 1
EX4
If P42 = VCM and P3 = 2
6
If P42 = VCM and P3 = 2
No
If P42 = VCM and P3 = 2
15
If P42 = VCM and P609 = Yes and P3 = 2
50
If P42 = VCM and P3 = 2
23