Hourly Programming; Presentation; Definition Of The Programming Stages; Definition Of Holiday Zones - Carrier 30WI Manual

Chiller - heat pump control
Table of Contents

Advertisement

26 - HOURLY PROGRAMMING

26.1 - Presentation

This function allows the weekly management of liquid chillers by selecting :
- 6 programming stages (maxi).
- 6 holidays zones (maxi).

26.2 - Definition of the programming stages

Setting :
Starting time
Ending time
Selected days (M.T.W.T.F.S.S.)
Type of regulation: Setting 1 – Stop/Setting 2 – Stop/setting 1 – setting 2 / setting 2 – setting 1/non valid.
Setting by fault :
Starting hour: 0h00
Ending hour: 0h00
Validated days: none
Type of regulation not validated.

26.3 - Definition of holiday zones.

Settings:
Type of zone: non valid, stop, running on setting 1, running on setting 2.
Starting date dd-mm
Ending date dd-mm
Setting by fault Non valid, from 01-01 to 01-01

26.4 - Operation

When putting under voltage or when setting the time, the information on the machine status are updated as a function of the programming
settings.
The user can change the status of his unit (Run/Stop – ½ setting regulation) but if a time range or a holiday zone is active, the information
will be updated at the starting or ending time of the programming
In the case where at least one time range or one holiday zone is validated, the parameter P120 is forced on « 2 per console or BMS
» and cannot be modified.
When going under test mode, the programming becomes non active. When leaving the test mode, the unit status information are
updated as a function of the programming settings.
In case of range overlapping, the running mode has priority over the stop mode and setting 1 over setting 2.
Same thing in case of overlapping of zones
If a programme stage is active (# non validated) and the real day is selected, the status of the unit is as follows :
Type of programme
CSG1 -stop
CSG2 -stop
STP1-STP2
STP2-STP1
If at least one time range or one holiday zone is validated, alternate the message machine stopped or setting/temp with a
message in order to signal to the user that the status will be updated on next status change of time range. Display of each
of these messages for 3 seconds.
■ Message to be displayed :
Status before starting time
Off
Off
Running on setting 2
Running on setting 1
H O U R L Y
P R O G R A M M I N G
O N
Status before starting time
and ending time
Running on setting 1
Running on setting 2
Running on setting 1
Running on setting 2
Status after ending time
Off
Off
Running on setting 2
Running on setting 1
113