Ac Output Over-Current Protection - Honeywell SMARTBOX Owner's Manual

Controller for wind turbine model wt6500
Table of Contents

Advertisement

SMARTBOX Installation

AC Output Over-current Protection

SMARTBOX™ Controller for HONEYWELL™ Wind Turbine WT6500 Owner's Manual - Rev14
The NEC/CEC requires the AC output circuit to be protected with a device rated for
125% of the rating of the circuit. The AC-rated fuse or circuit breaker between the
battery and the SMARTBOX™ Controller must have a maximum size of 15A (the
maximum current rating of the SMARTBOX™ Controller).
SHOCK OR FIRE HAZARD
A maximum of a 15amp over-current protection must be
installed to protect the SMARTBOX™ Controller from
short circuits and to provide a means of disconnecting the
SMARTBOX™ Controller. Failure to follow this warning
may result in death, personal injury or property damage.
Turbine SMARTBOX™ Controller
(2) #12 THWN-2
+ #6 GND
¾" CONDUIT
15 AMP FUSE OR
BREAKER
L1
N
AC OUTPUT
TO SUB SWITCH
BOARD
SINGLE PHASE
120V 15AMP
Figure 2.11 AC Circuit Diagram
Get other manuals https://www.bkmanuals.com
AC IN
(2) #12 THWN-2
+ #6 GND
¾" CONDUIT
L1
AC INPUT
FROM MAIN SWITCH
SINGLE PHASE
120V 15AMP
GND
N
GND
BOARD