12.0 OPERATION AND INSPECTION CHECKLIST

Monitor must be inspected for proper operation and function according to this checklist before each use. Before flowing water check:
1) There is no damage to the appliance that could impair safe
operation (e.g. dents, cracks, corrosion, missing, broken or
loose parts, damaged markings, or other defects)
• Waterway is clear of obstructions
• Gaskets are in good condition
• Hose and nozzle are securely attached.
• The pressure setting on the relief valve (if so equipped)
is set correctly
2) Hose and nozzle are securely attached.
3) Both legs are fully open.
4) All three spikes are in contact
with the ground.
5) Valve handle locks when closed
and releases.
Locks
and Unlocks
6) Inlet coupling swivels freely
when hose is charged.
WARNING
TASK FORCE TIPS LLC
MADE IN USA · tft.com
©Copyright Task Force Tips LLC 2006-2023
Charged Hose
Equipment failing any part of the checklist is unsafe for use and must have the problem corrected
before use or being placed back into service. Operating equipment that has failed the checklist is a
misuse of this equipment.
7) Monitor is anchored:
See Section 6
• Tied Off (required) • Hooked Leg • Spike Hold • Weight
8) Outlet pivots smoothly in both directions
and elevation safety plunger is operational.
9) Shut-Off valve is operational.
(see section 2.2)
10) Monitor is pointed in a safe direction.
3701 Innovation Way, Valparaiso, IN 46383-9327 USA