Enerzone SOLUTION 1.7 Owner's Manual page 21

Table of Contents

Advertisement

3.1.4
With Heat Shield AC02762 and Lowered Ceiling
To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used . Refer to the booklet in the screen options to obtain the dimensions to
be respected.
APPLIANCE CLEARANCES WITH DOUBLE
WALL PIPE CONNECTOR
Canada
A
2 ½" (64 mm)
B
2 ½" (64 mm)
C
2 ½" (64 mm)
78" (1981 mm)
L
DISTANCES
WITH DOUBLE WALL PIPE CONNECTOR
Canada
D
6" (152 mm)
E
11 ½" (292 mm)
F
11 ¼" (286 mm)
A
B
E
CAN
48"
122 cm
If the clearance reduction is on the same side as the door handle, position the stove at
a minimum of 6 inches from the side wall (clearance B), otherwise it may be located at
the clearance shown in the table above.
1
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
mentioned.
Installation and Operation Requirements - Solution 1.7
USA
2 ½" (64 mm)
2 ½" (64 mm)
2 ½" (64 mm)
78" (1981 mm)
FROM PIPE CONNECTOR
1
USA
6" (152 mm)
11 ½" (292 mm)
11 ¼" (286 mm)
D
48"
US
Flush
36"
92 cm
Ve
Ho
C
F
F
L
Page 21