Page 1
— SA F E T Y PR OD U CTS Tina 3A/3Aps Adapter unit Product Manual 2TLC172125M0201 Rev.F ORIGINAL INSTRUCTIONS new.abb.com/low-voltage/products/safety-products...
Page 2
Suitability for use ABB shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer’s application or use of the product. Third party certificates for the products are available at https://new.abb.com/low- voltage/products/safety-products.
This document is intended for authorized personnel. Reading prerequisites It is assumed that the reader of this document has knowledge of the following: • Basic knowledge of ABB safety products • Knowledge of machine safety Special notes Pay attention to special notes in the document:...
Safety Safety precautions The safety precautions must be followed during installation, operation, maintenance and troubleshooting. It is the responsibility of the user to ensure the correct overall functionality. Warning! Carefully read through the entire product manual before using the device. Warning! The devices shall be installed by authorized personnel following applicable Safety regulations, standards and the Machinery directive.
Product description Tina 3A and Tina 3Aps are used to adapt safety devices with mechanical contacts to the DYNlink safety circuit monitored by a safety controller or a safety PLC. Examples of such safety devices are emergency stops and switches or light curtains and light beams with internal relay outputs.
Installation • The Tina unit shall be attached to the M20 entry before the safety loops are connected to the device. • See max. tightening torques in chapter “Technical data”. Installation precautions Warning! To maintain highest safety level and reduce risk of electrical interference the unit shall be installed within the same physical encapsulation as the safety device.
Note! See connection cable cross section area and cable length in chapter 'Technical data/General'. Caution! All cable colors according to ABB standard cables. Warning! Information output signals shall never be used for safety purpose(s). Warning! The connection cables are not monitored and shall therefore be installed within the same physical enclosure as the safety device to maintain the highest safety level (fault exclusion, refer to EN ISO 13849-2:2012, Annex D).
Connection examples Tina 3A Caution! All cable colors according to ABB standard cables. Tina 3Aps Caution! All cable colors according to ABB standard cables. 2TLC172125M0201 Rev.F...
Functions LED Indications LED indication Description DYNlink state Green DYNlink input signal, both safety loops closed Green/red flashing DYNlink input open or 0 VDC, Interrupted before this both safety loops closed unit One or both safety loops open Interrupted in this unit Information output signal attributes The information output of the unit is set depending on the state of the internal safety loop A/B:...
(EN 62061:2005+A1:2013+A2:2015, EN ISO 13849-1:2015). Warning! In case of breakdown or damage to the product, contact ABB. Do not try to repair the product yourself since it may accidentally cause permanent damage to the product, impairing the safety of the device which in turn could lead to serious injury to personnel.
Troubleshooting LED indications LED indication Probable cause Action Device pushed/opened Check status of the device. Bad connection between Check terminals and fasten them loops (A and/or B) and carefully. device terminals +24 VDC connected to Check if there is +24 VDC on DYNlink signal input DYNlink signal input.
Address ABB Electrification Sweden AB SE-721 61 Västerås Sweden Order code/Ordering data 2TLA020054R0200: Tina 3A Adapter 2 contacts M12-5 2TLA020054R1400: Tina 3Aps Adapter 2 contacts + supply M12-5 Power supply Required power supply type PELV/SELV, not intended to be connected to a DC distribution network.
Page 15
Power output (Tina 3Aps only) Source current Maximum: 1 A General Protection class IP67 Ambient temperature Operation: -10 to +55 °C Storage: -30 to +70 °C Humidity range 35 to 85 % (with no icing or condensation) Housing material Connectors M12 5-pole male connector Cables Conductor cross section area: 0.34 mm...