Ambient temperature
Storage temperature
Resistance to alternating
temperature cycles
Climate class
Ingress protection
Vibration resistance
Electromagnetic compatibility
(EMC)
Process temperature
Process pressure
20
Operating conditions: Environment
-40 °C to +80 °C (-40 °F to +176 °F)
The functionality of the LC display becomes restricted at Tu<-20 °C (Tu<-4 °F) and Tu>+60 °C (Tu>140 °F).
If the device is operated outdoors in strong sunlight, you should use a protective cover → ä 39, "Weather
protection cover".
-40 °C to +80 °C (-40 °F to +176 °F)
to DIN EN 60068-2-14; Nb test : +80°C/-40°C, 1K/min, 100cycles
DIN EN 60068-2-38 (Test Z/AD) DIN/IEC 68 T2-30Db
• With closed housing, tested according to
– IP 68, NEMA 6P (24h at 1.83 m (6 ft) under water surface)
– IP 66, NEMA 4x
• With open housing: IP 20, NEMA 1 (also ingress protection of the display)
Caution!
Degree of protection IP 68 NEMA 6P applies for M12 PROFIBUS-PA plugs only when the PROFIBUS cable is
plugged in.
DIN EN 60068-2-64 / IEC 68-2-64: 20...2000 Hz, 1 (m/s
• Electromagnetic compatibility according to all relevant requirements of the EN 61326- series and NAMUR
recommendation EMC (NE21). For details see declaration of conformity.
• A standard installation cable is sufficient if only the analogue signal is used. Use a screened cable when
working with a superimposed communication signal (HART).
Operating conditions: Process
-40°C to +80°C (-40 °F ... +176 °F)
A temperature sensor is integrated in the sensor for correction of the temperature-dependent time-of-flight.
• FMU40/41: 0.7 bar to 3bar abs. (10.15 psi ... 43.5 psi abs.)
• FMU42/43/44: 0.7 bar to 2.5bar abs. (10.15 psi ... 36.25 psi abs.)
2
2
)
/Hz; 3 x 100 min
Prosonic M
Endress+Hauser