Page 1
Brief Operating Instructions Prosonic M FMU40/41/42/43/44 Ultrasonic Level Measurement These are Brief Operating Instructions. For more detailed information, please refer to the Operating Instructions and the additional documentation on the CD-ROM provided. These Brief Operating Instructions are not intended to replace the Operating Instructions provided in the scope of supply.
Ex document must be observed. The documentation number of the related Safety Instructions is also indicated. • If using devices for applications with safety integrity level, the separate manual on functional safety must be observed thoroughly (→ see CD-ROM). Endress+Hauser...
Pack the measuring instrument so that is protected against impacts for storage and transport. The original packing material provides the optimum protection for this. The permissible storage temperature is -40 °C ... +80 °C (-40 °F to +176 °F). Endress+Hauser...
Installation with counter nut Sealing ring (EPDM) supplied counter nut (PC) supplied for G 1½” and G 2” instruments Installation with adapter flange Installation with installation bracket ENDRESS+HAUSER Prosonic M Sealing ring (EPDM) adapter flange supplied nozzle sensor L00-FMU4KAxx-17-00-00-en-002 Endress+Hauser...
Page 6
Mounting Prosonic M FOUNDATION Fieldbus 2.2.2 Installation variants FMU42, FMU44 Installation with mounting bracket Installation with universal flange L00-FMU42xxxx-17-00-00-en-001 2.2.3 Installation variants FMU43 Installation with Installation with universal slip-on flange (option) mounting bracket slip-on flange sensor nozzle L00-FMU43xxxx-17-00-00-en-001 Endress+Hauser...
8 m (26 ft) 0.77 m (2.5 ft) FMU42 9° 10 m (33 ft) 0.79 m (2.6 ft) FMU43 6° 15 m (49 ft) 0.79 m (2.6 ft) FMU44 11 ° 20 m (66 ft) 1.93 m (6.3 ft) Endress+Hauser...
Page 8
Mounting Prosonic M FOUNDATION Fieldbus 2.3.2 Installation in narrow shafts In narrow shafts with strong interfe- rence echoes, we recommend using an ENDRESS+HAUSER ENDRESS+HAUSER ENDRESS+HAUSER ENDRESS+HAUSER Prosonic M Prosonic M Prosonic M Prosonic M ultrasound guide pipe (e.g. PE or PVC...
The interior of the nozzle must be smooth and may not contain any edges or welded joints. In particular, there should be no burr on the inside of the tank side nozzle end. Note the specified limits for nozzle diameter and length. To minimise disturbing factors, we recommend an angled socket edge (ideally 45°). Endress+Hauser...
Page 10
5 (16) 8 (26) 10 (33) 15 (49) 20 (66) in liquids Max. range [m (ft)] 2 (6.6) 3,5 (11) 5(16) 7 (23) 10 (33) in solids " Caution! If the blocking distance is undershot, it may cause device malfunction. Endress+Hauser...
Page 11
The sensor range is dependent on the measuring conditions. Refer to Technical Information TI 365F/00/EN for an estimation. The maximum range is shown in the above diagram (valid for good conditions). Sensor maximum range [mm (inch)] FMU40 5 (16) FMU41 8 (26) FMU42 10 (33) FMU43 15 (49) FMU44 20 (66) Endress+Hauser...
Proceed as follows to turn the housing to the required position: • Undo the fixing screws (1) • Turn the housing (2) in the required direction • Tighten up the fixing screws (1). Maximum torque 0.5 Nm (0.36 lbf ft). • Loctite can be used for securing the screw. Endress+Hauser...
• If available: Are the measuring point number and labelling correct (visual inspection)? • Is the measuring device sufficiently protected against precipitation and direct sunlight? • Are the cable glands tightened correctly? • After aligning the housing, check the process seal at the nozzle or flange. Endress+Hauser...
Screw on housing cover (1). Switch on power supply. 1 2 3 4 L00-FMxxxxxx-04-00-00-xx-032 Wiring with FOUNDATION Fieldbus connector Insert plug (1) into bushing (2). Screw firmly. Ground the device according to the desired safety concept. L00-FMP4xxxx-04-00-00-xx-004 Endress+Hauser...
Twisted, shielded pairs must be used. The cable specifications can be taken from the FF specification or IEC 61158-2. The following have been found suitable: Non-Ex-area: • Siemens 6XV1 830-5BH10, • Belden 3076F, • Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL. Ex-area: • Siemens 6XV1 830-5AH10, • Belden 3076F, • Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL. Endress+Hauser...
(e.g. ceramic 10 nF/250 V&). " Caution! Applications, which are subject to the explosion prevention, permit only under special conditions the repeated grounding of the protective screen , see to EN 60 079-14. Endress+Hauser...
• Are the terminals correctly assigned? • Is the cable gland tight? • If available: Is the FOUNDATION Fieldbus connector screwed tight? • Is the housing cover fully screwed on? • If power supply available: Does a display appear on the display module? Endress+Hauser...
Select the "tank properties" (002) function (where the existing tank shape is selected). 4.1.1 Identifying the functions For simple orientation within the function menus, for each function a position is shown on the display. L00-FMRxxxxx-07-00-00-en-005 The first two digits identify the function group: • basic setup • safety settings • linearisation Endress+Hauser...
U 16.. U 16.. 4...2 4...2 . 20 . 20 0 mA 0 mA V DC V DC >70 >70 °C °C t >85° t >85° Symbols ENDRESS + HAUSER – 3 keys snap-fit L00-FMxxxxxx-07-00-00-en-001 Endress+Hauser...
Page 21
L00-FMxxxxxx-07-00-00-en-002 In the measured value display, the bargraph corresponds to the output.The bargraph is segmented in 10 bars. Each completely filled bar represents a change of 10% of the adjusted span. Endress+Hauser...
Page 22
Contrast settings of the LCD Hardware lock / unlock After a hardware lock, an operation of the instrument via display or communication is not possible! The hardware can only be unlocked via the display. An unlock parameter must be entered to do so. Endress+Hauser...
Select the basic unit (this message appears the first time the instrument is switched on) ⇓ The current measured value is displayed ⇓ After is pressed, you reach the group selection. This selection enables you to perform the basic setup Endress+Hauser...
This function displays the current measured value in the selected unit (see "customer unit" (042) function). The number of digits after decimal point can be selected in the "no.of decimals" (095) funtion. 5.4.2 Function group "basic setup" (00) ⇒ ENDRESS + HAUSER – Endress+Hauser...
Page 25
• dome ceiling (→ A) • horizontal cyl. (→ B) • bypass (→ C) • stilling well (ultrasonic guide pipe) (→ D) • no ceiling (→ E) • sphere (→ F) • flat ceiling (→ G) ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-14-00-06-de-001 Endress+Hauser...
Page 26
ENDRESS + HAUSER – This function is used to select the process conditions: Selection: • standard • calm surface • turb. surface • add. agitator • fast change • standard solid • solid dusty • conveyor belt • Test: no filter Endress+Hauser...
Page 27
L00-FMU4xxxx-14-00-00-xx-003 L00-FMU4xxxx-14-00-00-xx-004 L00-FMU4xxxx-14-00-00-xx-006 solid dusty conveyor belt Test: no filter Dusty bulk solids Bulk solids with rapid level change All the filters can be switched off for purposes of service and diagnosis. ENDRESS+HAUSER Prosonic M L00-FMU4xxxx-14-00-00-xx-007 L00-FMU4xxxx-14-00-00-xx-005 Endress+Hauser...
Page 28
ENDRESS + HAUSER – In this function the blocking distance (BD) of the sensor is displayed. " Caution! When entering the full calibration (span), please take into account, that the maximum level may not project into the blocking distance (BD). Endress+Hauser...
Page 29
This function triggers the mapping of interference echoes. To do so, the measured distance must be compared with the actual distance to the product surface. The following options are available for selection: Selection: • distance = ok • dist. too small • dist. too big • dist. unknown • manual Endress+Hauser...
Page 30
This value can be edited by the operator.For manual mapping, the default value is: 0 m. " Caution! The suppression range must end 0.5 m in front of the echo of the actual level. With an empty tank, do not enter E but E – 0.5 m. Endress+Hauser...
Page 31
5.7.6 Return to group selection After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("display" (09) function group) is recommended. ⇒ ENDRESS + HAUSER – ⇓ After 3 s, the following message appears Endress+Hauser...
• cyclic Note! If the envelope curve mode is active on the display, the measured values are updated in a slower cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has been optimised. Endress+Hauser...
Page 33
Prosonic M FOUNDATION Fieldbus Commissioning Endress+Hauser...
Page 34
Commissioning Prosonic M FOUNDATION Fieldbus Endress+Hauser...
Page 35
Prosonic M FOUNDATION Fieldbus Commissioning Endress+Hauser...