Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
AC Reclosers
Power to operate the tripping and closing solenoids in the
recloser is provided by the power capacitor located
behind the operator panel of the control. A sealed, 24-volt,
lead acid battery is located in the lower portion of the con-
trol cabinet and is utilized to provide operating and trip-
ping energy when AC power is temporarily lost. The
control is equipped with an ac-powered, temperature-
compensated battery charger.
Operation Upon Loss Of AC Power
If the control is equipped with the standard 24 Vdc lead-
acid battery, the control maintains full operation from the
battery power supply for a minimum of 32 hours at 20°C
(24 hours at -40°C). To prevent battery damage, the con-
trol shuts down automatically upon detection of low bat-
tery voltage below 22.7 Vdc.
Control programming settings and parameters—including
event recorder, duty monitor, and data profile metering
parameters—are stored in non-volatile memory and
retained upon loss of control power. The time/date clock
resets to 0:00:00, 1970 upon loss of control power.
LED Indicators
CLOSE Pushbutton
TRIP (LOCKOUT)
Figure 2.
Form 5 recloser control operator panel.
4
LCD Display
CONTROL OK
AC POWER
ABOVE MIN TRIP
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
SENSITIVE-GROUND FAULT TARGET
BUSHINGS 1-2 VOLTAGE
BUSHINGS 3-4 VOLTAGE
BUSHINGS 5-6 VOLTAGE
RECLOSER CLOSED
RECLOSER OPEN
CONTROL LOCKOUT
Pushbutton
TRIP
(LOCKOUT)
The AC power LED indicator on the operator panel of the
control will turn off after 15 seconds upon loss of AC
power. The indicator will illuminate immediately upon
return of ac power.

Initializing the Control

Two methods are available to initialize the Form 5 control.
Method 1: Connect AC power to the input connector ter-
minal TB-1. Refer to the Customer Connec-
tions for AC Power section of this manual.
Method 2: Connect the battery terminal on the control
and press the MANUAL BATTERY RECON-
NECT button located on the Form 5 power
supply. See Figure 4.
Note: Method 2 powers the control off the battery
In both methods, after initialization, set the control clock
via the interface software.
BACK
NEXT
RESET
CHANGE
TARGETS
RESET
LAMP
MAX CURRENT
TEST
GND TRIP
NON
SUPERVISORY
RECLOSING
BLOCKED
BLOCKED
COLD LOAD
FAST
BATTERY
PICK UP
TRIPS
TEST
BLOCKED
DISABLED
ALTERNATE
ALTERNATE
ALTERNATE
PROFILE
PROFILE
PROFILE
NO. 1
NO. 2
NO. 3
TX 2
TX 3
HOT LINE
TAG
ON
RS232
RX 3
RX 2
OFF
®
KYLE
CLOSE
FORM 5
RECLOSER CONTROL
and is not intended for long term operation.
LCD Display Dedicated
Function Keys
Operation "Hot Keys"
RS232 Data Port
Hot Line Tag
99005KM

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kyle form 5Form 5 udpForm 5 dc nova

Table of Contents