Mounting The Control - Cooper S280-79-10 Install And Operation Instructions

Microprocessor-based recloser controls
Table of Contents

Advertisement

SAFETY
FOR LIFE

Mounting the Control

Mount the Form 5 recloser control in a convenient, acces-
sible location. Mounting dimensions are provided in Fig-
ure 28.
• For pole-mounted installation, a hole and keyway in
the control mounting bracket accommodates a 5/8"
bolt.
• For substation installation, brackets are available as
an accessory for mounting the control to a substation
frame.
Female Receptacle
For Control
35mm (1-7/16") Dia. Hole
For User 120Vac
Input Connection
(Cap-Plug Installed)
110mm
(4-1/4")
40mm
(1-1/2")
30mm (1-1/8") Hole
In Lifting Lug
Male Receptacle
For Control Cable
CONTROL WEIGHT
Figure 28.
Control cabinet mounting dimensions.
Cable
Vent
130mm
(5-1/8")
190mm
(7-3/8")
200mm
(7-7/8")
380mm
(15")
160mm
(6-3/8")
685mm
(27")
350mm
30mm
(13-13/16")
(1-1/8")
52 kg (115 LBS)
Limits on control cable length are determined by the max-
imum distance between the control and recloser:
• Up to 410 m (125* ft) for solenoid-operated reclosers
(VWE, VWVE27, VWVE38X, WE, WVE27, WVE38X,
and NOVA).
• Up to 10,7 m (35* ft) for motor-operated reclosers
(VSA12, VSA12B, VSA16, VSA20, VSA20A, VSO12,
VSO16).
Up to 41 m (135* ft) for NOVA DC.
* These lengths are based on standard control cables.
Consult your Cooper Power Systems representative if
longer cable lengths are required.
C L
120mm (4-3/4")
45mm (1-3/4") Dia. Hole
For Automation Accessory
(Cap-Plug Installed)
C L
480mm
(19")
240mm
(9-1/2")
76mm
(3")
Die-cast-zinc latchable
Handle For User-
Provided Utility-Grade
Padlock
110mm
(4-3/8")
165mm
(6-1/2")
S280-79-10
Mtg Hole For
15mm (5/8") Max
Bolt Dia.*
* USER-PROVIDED HARDWARE
40mm (1-1/2")
Grounding Terminal
One Internal and
One External
Use No. 14 To No. 4
Stranded Wire
33