Standard And Udp Dif Module 1 Inputs - Cooper S280-79-10 Install And Operation Instructions

Microprocessor-based recloser controls
Table of Contents

Advertisement

Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The DIF inputs are factory-configured as momentary (0.25 sec. duration) or maintained functions. Supervisory signals
do not have any effect when supervisory blocked is active. Remote inputs function when supervisory is blocked.
Input
Connector
1
P4-1
2
P4-2
3
P4-3
4
P4-4
5
P4-5
6
P4-6
7
P4-7
8
P4-8
Note: Supervisory Alternate Profile 3 replaced by Switch
Mode on UDP controls.
26
Standard and UDP Control DIF Module 1
Function
Supervisory Trip and Lockout
Supervisory Close
Remote Hot Line Tag
Supervisory Ground Trip Block
Supervisory Alternate Profile 1
Supervisory Alternate Profile 2
Supervisory Alternate Profile 3*
Supervisory Normal Profile
Inputs
Supervisory Trip and Lockout trips the recloser open and locks out
the control. The control remains locked out until closed manually or
by the supervisory close feature. A momentary signal is required.
Supervisory Close initiates a closing signal to the recloser. A
momentary signal is required for proper operation.
Remote Hot Line Tag performs the same functions as the HOT
LINE TAG switch on the operator panel. Remote Hot line Tag is
activated by a maintained SCADA command, a serial command,
or locally via a operator panel switch. This input is active regardless
of the state of the supervisory function.
Supervisory Ground Trip Block provides supervisory operation of
ground trip block by a remote momentary signal.
This input performs the same function as the GND TRIP BLOCKED
key on the operator panel. This input is inactive if the Supervisory
function is disabled.
Supervisory Alternate Profiles provides selection of alternate pro-
grammed values for phase and ground. This feature is activated by
a remote momentary signal.
These inputs are active with a momentary whetting voltage and
cause the control to select the respective Supervisory Alternate Pro-
file. The inputs are inactive if the Supervisory function is disabled.
Supervisory Normal Profile requires a momentary signal for proper
operation.
This input is active with a whetting voltage and causes the control
to select Normal Protection Profile. This input is inactive if the
Supervisory function is disabled.
Description