Connection of the data
cable to the control unit
ST-S
Note:
Keep the distance of the
data cable between the
webmodule and the con-
trol unit ST-S as short as
possible. Please avoid a
wiring around the char-
ging unit.
4.3 Commissioning the
Webmodule on the
ZB-S
After connection of the
power supply (24V DC), the
webmodule needs approx.
1.5 minutes for booting.
After the booting, the red
LED of the webmodule
flashes slowly. To log on
the webmodule on the ST-S
control unit, the service pin
of the webmodule must
be pressed for approx. 1
second.
The menu „webserver
setup" appears in the
display of the control unit
of the ZB-S. During the log
on procedure the display
shows a lot of question
marks.
After approx. 3-5 seconds
the display shows the
standard settings of the
webmodule:
Operating Instructions
Webmodule ZB-S
The webmodule gets
automatically activated to
the control unit, which is
displayed by the red LED
(some seconds) of the con-
trol unit and the webmo-
dule. After 1-2 minutes the
procedure is finished and
the webmodule is ready to
operate.
LED-display of the web-
module:
LED flashes slowly:
webmodule is not activated
on the control unit.
Status-LED flashes fastly
3x :
when pushing the service
pin for approx. 10 seconds
the webmodule will be set
back into delivery status.
Service pin of the webmo-
dule:
Pressing the service pin for:
1 sec.: login/logout of the
webmodule on the control
unit ST-S
> 10 sec.: resets the modu-
le to the delivery status
Attention!
All programmed data get
lost!
4.4 Deactivate the
webmodule on the
control unit ZB-S
The webmodule can be
deactivated on the control
unit. For this, the service
pin of the webmodule has
to be pressed for approx. 1
sec. The screen showed in
the picture above appears.
With the push button „arrow
left" or „arrow right" the
webmodule can be set as
„not installed". Press o.k.
and back with menu button.
Now the webmodule is off-
line and the red LED flashes
slowly.
CEAG Notlichtsysteme GmbH