Standard And Udp Dif Module 1 Outputs - Cooper S280-79-10 Install And Operation Instructions

Microprocessor-based recloser controls
Table of Contents

Advertisement

Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The 12 outputs of the DIF Module are Form C relay contacts. Six of the outputs are latching and six are non-latching.
Note: Contacts shown in inactive mode.
Output Connector
1
P3-1 NC
Normal Profile
P3-2 NO
2
P3-3 NC
Non-Reclosing
P3-4 NO
3
P3-5 NC
Cold-Load Pickup Blocked
P3-6 NO
4
P3-7 NC
Supervisory Blocked
P3-8 NO
5
P3-9 NC
AC power
P3-10 NO
6
P3-11 NC
Control OK
P3-12 NO
7
P2-1 NO
Recloser Open
P2-2 NC
8
P2-3 NO
Hot Line Tag
P2-4 NC
9
P2-5 NO
Ground Trip Blocked
P2-6 NC
10
P2-7 NO
Alternate Profile 1
P2-8 NC
11
P2-9 NO
Alternate Profile 2
P2-10 NC
12
P2-11 NO
Alternate Profile 3*
P2-12 NC
*Note: Supervisory Alternate Profile 3 replaced by Switch
Mode on UDP controls.
28
Standard and UDP Control DIF Module 1
Function
Non-Latched
Non-Latched
Non-Latched
Non-Latched
Non-Latched
Non-Latched
Outputs
Type
Normal Profile is active only when Alternate Profiles are
inactive. Normal reclosing operations will follow.
This output is active when the NON-RECLOSING indicator
in the operator panel is illuminated.
This output is active when the COLD LOAD PICKUP
BLOCKED indicator on the operator panel is illuminated.
Supervisory Blocked prevents operation from supervisory
control. Programming is accessible from the operator panel.
This output is active when the SUPERVISORY BLOCKED
indicator on the operator panel is illuminated.
AC power indicator is active when the control detects the
presence of AC power. This output is active when the AC
power indicator on the operator panel is illuminated.
Control OK indicator is active when the control is able to per-
form protection operations. This output is active when the
CONTROL OK indicator on the operator panel is illuminated.
Latched
Recloser Open indicator is active when the recloser signals
the control that the recloser contacts are open. This output is
active when the RECLOSER OPEN indicator is illuminated.
Latched
With Hot Line Tag active, close circuit is disabled and the
HOT LINE TAG indicator is illuminated. With Hot Line Tag
inactive, the control switched back to the previous time cur-
rent curve for the active profile, close circuit is enabled and
the HOT LINE TAG indicator is off. This output is active
when the operator panel indicator is illuminated.
Ground Trip Blocked causes the control to block ground trip-
Latched
ping operations. This output is active when the GND TRIP
BLOCKED INDICATOR on the operator panel is illuminated.
Latched
These outputs are active when the respective ALTERNATE
PROFILE indicators on the operator panel is illuminated.
Latched
Latched
Description