Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The 12 outputs of the DIF Module are Form C relay contacts. Six of the outputs are latching and six are non-latching.
Note: Contacts shown in inactive mode.
Output Connector
1
P3-1 (NC)
Control Lockout
P3-2 (NO)
2
P3-3 (NC)
Check Battery
P3-4 (NO)
3
P3-5 (NC)
Reverse Power Flow
P3-6 (NO)
4
P3-7 (NC)
Fast Trips Disabled
P3-8 (NO)
5
P3-9 (NC)
Operation Counter
P3-10 (NO)
6
P3-11 (NC)
Recloser Malfunction
P3-12 (NO)
7
P2-1 (NO)
Bushings 1-2 Fault Target
P2-2 (NC)
8
P2-3 (NO)
Bushings 3-4 Fault Target
P2-4 (NC)
9
P2-5 (NO)
Bushings 5-6 Fault Target
P2-6 (NC)
10
P2-7 (NO)
Ground Fault Target
P2-8 (NC)
11
P2-9 (NO)
Sensitive Ground Fault Target
P2-10 (NC)
12
P2-11 (NO)
Sensitive Ground Fault Blocked
P2-12 (NC)
30
Standard and UDP Control DIF Module 2
Function
Outputs
Type
Non-Latched
This output is active when the CONTROL LOCKOUT
indicator is illuminated.
Non-Latched
This output is active when the CHECK BATTERY indi-
cator is illuminated.
Non-Latched
This output is active when the REVERSE POWER
FLOW indicator is illuminated.
Non-Latched
This output is active when the FAST TRIPS DIS-
ABLED indicator is illuminated.
Non-Latched
If the Supervisory function is enabled, this output is
active when the OPERATION COUNTER OFF inputs
from Comm Port 1-DIF2, Comm Port 2 and Comm Port
3 are not active.
Non-Latched
This output is active when the RECLOSER MAL-
FUNCTION indicator is illuminated.
Latched
This output is active when the BUSHINGS 1-2 FAULT
TARGET indicator is illuminated.
Latched
This output is active when the BUSHINGS 3-4 FAULT
TARGET indicator is illuminated.
Latched
This output is active when the BUSHINGS 5-6 FAULT
TARGET indicator is illuminated.
Latched
Output is active when the GROUND FAULT TARGET
indicator is illuminated.
Latched
Output is active when the SENSITIVE GROUND
FAULT TARGET indicator is illuminated.
Output is active when Sensitive Ground Fault is
Latched
blocked.
Description

Hide quick links: