Form 5 Universal Device Protection (Udp); Control - Cooper S280-79-10 Install And Operation Instructions

Microprocessor-based recloser controls
Table of Contents

Advertisement

SAFETY
FOR LIFE
FORM 5 UNIVERSAL DEVICE PROTECTION (UDP) CONTROL
The UDP function allows the Form 5 control to become a
switch control to provide indication of overcurrent trip con-
ditions without issuing an overcurrent trip signal. The con-
trol is in the recloser mode when the feature is in the OFF
position, and in the switch mode when the feature is
ACTIVE.
While in the switch mode, all automatic open and close
operations of the recloser (including overcurrent voltage
and frequency) are blocked. Fault targeting, metering,
alarms, and event recording functions are active.
This non-tripping fault indication state is initiated via a
operator panel pushbutton (labeled SWITCH MODE), dig-
ital SCADA, or discrete SCADA. The UDP feature has
local indication at the operator panel (LED), digital indica-
tion, and remote indication via status contacts on the Dis-
crete Interface (DIF) module 1.
GND TRIP
BLOCKED
RECLOSING
COLD LOAD
BATTERY
PICKUP
BLOCKED
ALTERNATE
ALTERNATE
PROFILE
NO. 1
Figure 20.
Function/Indication pushbuttons for the Form 5
equipped with the UDP accessory.
SUPERVISORY
NON
BLOCKED
FAST
TRIPS
TEST
DISABLED
SWITCH
PROFILE
MODE
NO. 2
Figure 21.
Interface software Switch Mode settings.
CONTROL OK
AC POWER
ABOVE MIN TRIP
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
SENSITIVE-GROUND FAULT TARGET
SOURCE
VOLTAGE
LOAD
VOLTAGE
HOT LINE
RECLOSER CLOSED
TAG
RECLOSER OPEN
CONTROL LOCKOUT
TRIP
CLOSE
(LOCKOUT)
Figure 22.
Form 5/UDP Operator Panel.
S280-79-10
BACK
NEXT
RESET
CHANGE
TARGETS
RESET
LAMP
MAX CURRENT
TEST
GND TRIP
NON
SUPERVISORY
RECLOSING
BLOCKED
BLOCKED
COLD LOAD
FAST
BATTERY
PICK UP
TRIPS
TEST
BLOCKED
DISABLED
SWITCH
ALTERNATE
ALTERNATE
PROFILE
PROFILE
MODE
NO. 1
NO. 2
TX 3
TX 2
ON
RS232
RX 3
RX 2
OFF
®
KYLE
FORM 5/UDP
RECLOSER CONTROL
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Kyle form 5Form 5 udpForm 5 dc nova

Table of Contents