23: Remote Reset Enable

Option 1 enables remote resets via the plug-by or plug-on communicator, or
via a Downloader PC. This option is relevant only when the system is set up
for engineer resets (Command 33, option 1).
After an alarm, the user can silence the sounders, but can reset the system
only after contacting an Alarm Receiving Centre (ARC). The ARC verifies the
user's identity and can send a signal to the remote reset input of the plug-
on/plug-by port to enable the system to be reset using a normal user access
code. Use option 0 (the default) to disable this function. See also Command
50.
Note: To comply with PD 6662 / prEN 50131-1: 2004, the system must be set to hide
status information after 30 seconds (Command 28), in which case the Service lamp
will go out after the same period.

24: Show Control Unit Account Name

An account name can be programmed into a control unit using Downloader.
Use this command to display the account name.

25: Internal Sounder Delay and Duration

Option 0 (the default) makes the internal sounder use the external Bell Delay
and Duration times. Option 1 makes the internal sounder continue after the
external Bell Delay expires, stopping only when a user enters an access code.

26: Internal Sounder Delay on Entry

This command controls when internal sounders start to operate in response to
an intruder straying from the Entry Route or the entry time expiring.
If you select option 0, the control unit starts the internal sounders immediately.
If you select option 1 (the default), the control unit starts the internal sounders
at the same time as the external sounders (that is, after any Bell Delay). This
delay allows silent communications when an entry alarm is triggered, which is
required by some police forces. Option 1 is available only when:
° Alarm Abort is Off (Command 36, option 0)
° Bell Delay is not zero (Command 41, not option 0)
° Alarm Confirm is Off (Command 89, option 0)
Note: Compliance with PD 6662 / prEN 50131-1: 2004 (see page 86) at Grades 1, 2 and
3 requires that Command 26 is set to option 0.

27: Exit Fault External Sounder

This command controls what happens when an exit timer completes and a
zone is still violated (for example, when a door is not shut).
497096, Issue 6
2. Programming Commands
Page 15