5 Installation

The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.

5.1 Installation conditions

Work position
The work position is the front view onto the
operating controls on the device seen from
the position of operating personnel.
Operators must ensure that, after installation
of the device, the operating personnel can
perform all necessary work safely and easily
access the device from the work position.
Mounting orientation
The valve can be mounted in any desired
position.

5.2 Preparation for installation

Before installation, make sure the following
conditions are met:
− The converter is not damaged.
− The connections of the converter are
clean.
Proceed as follows:
Î Lay out the necessary material and tools
to have them ready during mounting.
EB 6132 EN

5.3 Mounting the converter

The converter is mounted on a top-hat rail
(DIN EN 60715).
Î Snap the converter onto the top-hat rail.

5.4 Adjusting the output signal

The converter is delivered with the output
signal range specified in the order. If a dif-
ferent output signal range is required than
the one specified on the nameplate, proceed
as follows:
Î Use a small screwdriver to lever off the
plate with the pneumatic connection.
Î Take the electronics unit out of the hous-
ing and pull the printed circuit boards
apart.
Î Adjust the rotary switch S2 and slider
switches S1.1 and S1.2 to se the re-
quired output signal (see Table 5-1).
Table 5-1: Switch settings for output signal
range
Output sig-
nal
S2
0 to 20 mA
4 to 20 mA
0 to 10 V
2 to 10 V
0 to 5 V
1 to 5 V
Installation
S1.1
S1.2
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON