Installation

3 Installation

3.1 Mounting position

The converter is to be installed horizontally,
with the pressure gauge (or screw plug) fac-
ing upward. If a different mounting position
is used, the zero point must be readjusted as
described in section 4.1 on page 10.
With degree of protection IP 54, the vent
plug must always be installed facing down-
ward to the floor.
Wall and pipe

mounting

Top view
2
Plate
3
Rail
4
M6 x 16 screw
5
M6 x 25 screw
6
Spring washer B6
7
A6.4 washer
8
M8 nut
9
A8.4 washer
10
M8 x 25 screw
11
Clamp
13
Wall or pipe bracket
Fig. 4: Mounting
8
7 6
5
Clamp for
attachment to
2" pipe
8 9
13
12
3.2 Mounting
The converter can be mounted to a wall, a
pipe or directly to a control valve (Fig. 4).
The following accessories are required:
Order no. 1400-6216
− For wall and pipe mounting
Order no. 1400-6217
− For attachment to valve with cast yoke
Order no. 1400-6218
− For attachment to valve with rod-type
yoke
See section 10.1 on page 24 for further
mounting parts.
Valve with cast yoke/rod-
type yoke mounting
Side view
Top view
6
4
7
3
6
5
2
8 9
10
Yoke
bracket
Rod-type yoke
bracket
EB 6116 EN
11