How To Change Binary Input/Output Signals Using Forcing; Forcing By Using Lhmi - ABB Relion 650 Series Commissioning Manual

Line differential protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 395-UEN Rev. G
Use the TESTMODE function block, appropriately configured in PCM600/ACT.
It may be convenient to control the input on mentioned component from, for example, an LHMI
function key or similar during commissioning to quickly and easily enter IED test mode.
8.8.3

How to change binary input/output signals using forcing

Once the IED is in IED test mode, the LHMI/PCM600 menus can be used to control input/output
signals freely.
8.8.3.1

Forcing by using LHMI

Editing a signal value directly
Edit the input/output value directly to select the desired logical level, by doing following:
1.
2.
3.
When navigating away from a LHMI forcing menu for an I/O board, the user is prompted to either
leave the signals forced, or to revert all of them back to the unforced state.
Line differential protection RED650
Commissioning manual
Select the value line of the desired signal, see figure 10.
Press the Enter key to edit the value.
IEC15000021 V1 EN-US
Figure 10:
Value line of the desired signal
Use the up/down arrows on the LHMI to change the signal value or the appropriate menu
in PCM600.
The status of the signal changes automatically to Forced (i.e. there is no need to set the
status to Forced manually).
On the LHMI, these edit changes have immediate effect. This means that the value
changes directly when the up/down arrow is pressed (i.e. there is no need to press
the Enter key to effectuate the change).
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 8
Testing IED operation
GUID-7DF9FAF1-68B1-49AF-9DE4-2A8D6F6FAEFE v2
GUID-D885671F-79E5-4B75-8777-B59E44F6FCFC v1
GUID-E0C115BE-3AD1-48C7-BA2D-29857CD3D3ED v1
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red650

Table of Contents