Repair Instruction - ABB Relion 650 Series Commissioning Manual

Line differential protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 395-UEN Rev. G
1.
Switch the IED off and insert the new module.
2.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
3.
Perform a license update in PCM600.
The new module is now available in PCM600 and is ready to be configured.
Removing a module from an IED
Procedure:
1.
Remove all existing configuration for the module in PCM, and write that configuration to the IED.
2.
Switch the IED off and remove the HW module.
3.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
4.
Perform a license update in PCM 600.
Moving a module in an IED from one position to another
Procedure:
1.
Remove all existing configuration for the module in PCM, and write that configuration to the IED.
2.
Switch the IED off and move the HW module.
3.
Switch the IED on, wait for it to start, and then perform a HW reconfig.
4.
Perform a license update in PCM600.
The new module is now available in PCM600 at the new position and is ready to be configured.
12.3

Repair instruction

An alternative is to open the IED and send only the faulty circuit board to Hitachi Power grids for
repair. When a printed circuit board is sent to Hitachi Power grids, it must always be placed in a
metallic, ESD-proof, protection bag. The user can also purchase separate replacement modules.
Most electronic components are sensitive to electrostatic discharge and latent damage may occur.
Please observe usual procedures for handling electronics and also use an ESD wrist strap. A semi-
conducting layer must be placed on the workbench and connected to earth.
Line differential protection RED650
Commissioning manual
If any configuration that makes the module needed remains, then the HW reconfig
will not remove the module.
The module will still be needed. An error indication for the module will appear, if the
module is physically removed from the IED and the IED is restarted with some part
of the configuration still requiring the module.
Never disconnect the secondary connection of a current transformer circuit without
short-circuiting the transformer's secondary winding. Operating a current transformer
with the secondary winding open will cause a massive potential build up that may
damage the transformer and may cause injuries to humans.
Never connect or disconnect a wire and/or a connector to or from a IED during
normal service. Hazardous voltages and currents are present that may be lethal.
Operation may be disrupted and IED and measuring circuitry may be damaged.
Strictly follow the company and country safety regulations.
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 12
Troubleshooting
IP8767-1 v1
M11764-2 v4
M11764-10 v2
M11766-4 v3
165