Emerson PACSystems RX3i Application Manual page 21

Genius dual bus
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

Application Guide
GFK-2928C
Figure 20: References by SBA of Genius Devices on Bus
BUS.Devices[nn].DI_Add
BUS.Devices[nn].DI_Len
BUS.Devices[nn].DQ_Add
BUS.Devices[nn].DQ_Len
BUS.Devices[nn].AI_Add
BUS.Devices[nn].AI_Len
BUS.Devices[nn].AQ_Add
BUS.Devices[nn].AQ_Len
Note:
Toolchest Components
B. For instance, a device configured at %AI0001 on Bus A must be
configured at %AI (1+AI_OFST) on Bus B.
This parameter applies to devices that contain discrete
inputs. It is the starting reference assignment for the device
installed at Serial Bus Address nn.
This parameter applies to devices that contain discrete
inputs. It is the number of inputs (i.e., length) associated
with the device installed at Serial Bus Address nn.
This parameter applies to devices that contain discrete
outputs. It is the starting reference assignment for the
device installed at Serial Bus Address nn.
This parameter applies to devices that contain discrete
outputs. It is the number of outputs
(i.e., length) associated with the device installed at Serial
Bus Address nn.
This parameter applies to devices that contain analog
inputs. It is the starting reference assignment for the device
installed at Serial Bus Address nn.
This parameter applies to devices that contain analog
inputs. It is the number of inputs (i.e., length) associated
with the device installed at Serial Bus Address nn.
This parameter applies to devices that contain analog
outputs. It is the starting reference assignment for the
device installed at Serial Bus Address nn.
This parameter applies to devices that contain analog
outputs. It is the number of outputs
(i.e., length) associated with the device installed at Serial
Bus Address nn.
Devices that contain outputs must be configured so that the dual mapping routine can post
loss-of-device or addition-of-device messages. Also, the device status (i.e., the presence on
either Bus A or Bus B) is shared between the Primary and Secondary PLCs for the purpose of
Automatic Role Switching (if enabled).