SiUS092230EA
6.2
Warmer Airflow Setting
Outline
The temperature of discharge airflow in heating operation can be adjusted warmer.
The room temperature will be high when getting close to the set temperature.
The discharge airflow does not become warmer in other than heating operation.
Procedure
Warmer airflow can be enabled from outdoor unit.
Cut the jumper (J5) of the PCB inside.
09/12 Class
15/18/24 Class
Reference
For the location of the jumper, refer to page 34, 36.
Note(s)
Warmer airflow can be enabled from either indoor or outdoor unit.
Warmer airflow becomes available when either one of the RC or outdoor unit setting is enabled.
For example, if the outdoor unit has the switch for warmer airflow, it can be set even when it is
disabled on the indoor unit.
Also, for the wireless remote controller with field setting function, warmer airflow is enabled when
set on indoor unit with the remote controller field setting, even when it is disabled on outdoor unit.
Part 7 Trial Operation and Field Settings
Field Settings for Outdoor Unit
Cut the jumper (J5).
Cut jumper (J5).
R7000387
R7000388