Summary of Contents for Daikin R32 split Series

  • Page 1 Installation manual R32 split series RXTM30N2V1B RXTM40N2V1B RXTP25N2V1B9 RXTP35N2V1B9 ARXTP25N2V1B ARXTP35N2V1B Installation manual English R32 split series RXTA30N2V1B...
  • Page 2 2P427092-18S...
  • Page 3 2P427092-18S...
  • Page 4 2P427092-12R...
  • Page 5 2P427092-12R...
  • Page 6: Table Of Contents

    To determine the complete recharge amount ..... 10 Daikin website (publicly accessible). 4.4.5 To charge additional refrigerant ........10 ▪ The full set of latest technical data is available on the Daikin 4.4.6 To fix the fluorinated greenhouse gases label .... 10 extranet (authentication required).
  • Page 7: Preparation

    Use a vibration-proof rubber (field supply) in cases where vibrations mentioned in "Sound spectrum" in the data book due to may be transmitted to the building. environmental noise and sound reflections. RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + Installation manual RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 8: To Install The Outdoor Unit

    Do NOT exceed the unit's maximum working pressure (see For information on the available options, contact your "PS High" on the unit name plate). dealer. Installation manual RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 9: To Perform Vacuum Drying

    ▪ After a leak. Charging additional refrigerant Before charging additional refrigerant, make sure the outdoor unit's external refrigerant piping is checked (leak test, vacuum drying). RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + Installation manual RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 10: To Determine The Additional Refrigerant Amount

    ▪ Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire. GWP × kg 1000 Installation manual RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 11: Specifications Of Standard Wiring Components

    NEVER operate the unit without thermistors and/or pressure sensors/switches. Burning of the compressor 2 Open the wire clamp. might result. 3 Connect the interconnection cable and power supply as follows: RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + Installation manual RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 12: Checklist Before Commissioning

    Daikin website (publicly accessible). Prerequisite: Power supply MUST be in the specified range. Prerequisite: Test run may be performed in cooling or heating ▪ The full set of latest technical data is available on the Daikin mode. extranet (authentication required).
  • Page 13 Compressor motor Fan motor Drain pump motor Swing motor MR*, MRCW*, MRM*, MRN* Magnetic relay Neutral n=*, N=* Number of passes through ferrite core Pulse-amplitude modulation RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + Installation manual RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 14: Piping Diagram: Outdoor Unit

    Accumulator Muffler ON: heating 4-way valve Discharge pipe thermistor Outdoor air temperature thermistor Compressor Propeller fan Fan motor High pressure switch (Automatic reset) Cooling Heating Installation manual RXTM30+40N2V1B + RXTP25+35N2V1B9 + ARXTP25+35N2V1B + RXTA30N2V1B R32 split series 3P482320-10M – 2019.04...
  • Page 16 3P482320-10M 2019.04...