Daikin RX-W Series Service Manual page 189

Hide thumbs Also See for RX-W Series:
Table of Contents

Advertisement

SiUS092230EA
Troubleshooting
In case of H9, J3, J6
J3 error: the discharge
pipe temperature is
lower than the heat
exchanger temperature.
H9 : Outdoor temperature thermistor
J3 : Discharge pipe thermistor
J6 : Outdoor heat exchanger thermistor
Reference
Check No.01 Refer to P.190
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn on the power again.
Error displayed
again on remote
controller?
YES
Check No. 01
Check the thermistor resistance
value.
Normal?
YES
Cooling: Outdoor heat
exchanger
temperature
Heating: Indoor heat
exchanger
temperature
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Indoor heat
exchanger thermistor
functioning?
YES
Troubleshooting for Outdoor Unit
NO
NO
NO
Reconnect the connectors
or thermistors.
Replace the defective
thermistor(s) of the following
thermistors.
∗ Outdoor temperature
thermistor
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger
thermistor
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB (main PCB).
(R20406)
183

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents