Output Specification; Transistor Output Processing - Xinje XSA330-W User Manual

Iot industrial controller
Table of Contents

Advertisement

4.3 Output specification

Normal transistor output:
External power
Circuit insulation
Action indicator
Max
Resistant load
load
Inductive load
Lamp load
Mini load
Response
OFF→ON
time
ON→OFF
Note: When the high-speed pulse output function is used, the controller can output 100KHz~200KHz
pulses, but it cannot ensure that all the servos operate normally.
Please connect a resistance of about 500 ohms between the output end and the 24V power supply.

4.4 Transistor output processing

Normal transistor output
Output Terminals
The transistor output of the controller unit has 2~3 common outputs.
External Power Supply
Please use DC5~30V power supply to drive the load.
Circuit Isolation
Inside PLC, we use photoelectric couplers to isolate between internal circuits and output
transistors; besides, the COM terminal blocks are separate from each other.
Below DC5~30V
Light coupling insulation
LED
0.3A
7.2W/DC24V
1.5W/DC24V
DC5V 2mA
Below 0.2ms
Below 0.2ms

Advertisement