Shut Down Button; Reset Button; Power Supply Input - Xinje XSA330-W User Manual

Iot industrial controller
Table of Contents

Advertisement

1.3.3 Shut down button

XSA330-W seriesis equipped with a shutdown button (pinhole structure), which can be forced to shut
down by pressing for 4 seconds, as shown in Figure 1-3.

1.3.4 Reset button

XSA330-W seriesis equipped with a Reset key (pinhole structure). Short press can restart the system.
Long press can reset the BIOS (clear CMOS) in power off status, as shown in Figure 1-4.
CMOS is powered by the button battery on the motherboard. Clearing CMOS will permanently erase
the previous system settings and set them to the original (factory setting) system settings. The steps
are as follows:
(1) Turn off the controller and disconnect the power supply
(2) Press the Clear CMOS key for 3-5 seconds with a slender pin, and then release it
(3) Start the controller, press the [Del] key to enter BIOS settings during startup, and reload the
optimal default value
(4) Save and Exit Settings

1.3.5 Power supply input

XSA330-W seriesis equipped with a 24V 4PIN phoenix terminal, as shown in Figure 1-5.
Please use the adapter or switching power supply provided with the device, and do not connect the
power supply with a voltage exceeding 25.2V, otherwise the motherboard will be burnt due to
overvoltage.
Yes (power off): red, normally on
Figure 1-3 shut down button
Figure 1-4 Reset button
Figure 1-5 power supply input interface